Final | 2/12/2020 | 2/13/2020 | 2/13/2020 | A | PASS |
Brian Scoles
|
|
|
Please call MJ on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
|
Final | 2/11/2020 | 2/11/2020 | 2/11/2020 | P | FAIL |
Brian Scoles
|
|
|
Please call the homeowner when on way: ###-#### M.J. Phone #: ###-#### Inspection requested via web by Arielle Hendricks- 1- need locking caps on a/c service ports- 2- need co detectors installed 3- need to remove 2 adjustable 90 degree that were used to make staight duct off furnace flue and run in pipe with 1/4 inch per foot rise to wye branch and support flue 4- need 3 screws per joint on flue missing a few
|
Final | 2/6/2020 | 2/11/2020 | 2/11/2020 | A | CANC |
Brian Scoles
|
|
|
Please call the homeowner when on way: M.J. Richards ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- per phone call with homeowner will reschedule- has morning appoinment wont be home
|
Issue PAID IN FULL permit | | | 2/5/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/5/2020 | | DONE |
|
|
|
This permit was created on the web by Arielle Hendricks
|