Conference | 6/23/2020 | 6/26/2020 | 6/26/2020 | A | CANC |
Brian Scoles
|
|
|
8am or early as possible Phone #: ###-#### Inspection requested via web by Edward Emmel- should have been final
|
Final | 6/26/2020 | 6/26/2020 | 6/26/2020 | A | PASS |
Brian Scoles
|
|
|
8am or early as possible Phone #: ###-#### Inspection requested via web by Edward Emmel- live gas test on csst at furnace locations and range with bubbles- no leaks observed
|
Pressure Test | 2/28/2020 | 3/3/2020 | 3/3/2020 | A | FAIL |
Brian Scoles
|
|
|
call Diane ###-#### before arrival- 815-830am- gas line needs to be tested to 20lb on 30lb psi gauge max- if live test with gas on one side of valve will need open tee and another shutoff valve installed or section test csst before hooking onto live gas system- do not use gas as installed now- shut off valve is closed at furnace location til pressure test witnessed- went over onsite with homeowner- will reschedule
|
Pressure Test | 2/28/2020 | 2/28/2020 | 2/28/2020 | P | CANC |
Brian Scoles
|
|
|
Ed Phone #: ###-####- reschedule for 3-3-20 am per phone call from Diane
|
Issue PAID IN FULL permit | | | 2/18/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/18/2020 | | DONE |
|
|
|
This permit was created on the web by Edward Emmel
|