Final | 4/9/2020 | 4/9/2020 | 4/9/2020 | P | PASS |
Jack Reynolds
|
|
|
Marko ***cleared*** Phone #: ###-#### - final ok
|
Rough-in | 2/27/2020 | 2/27/2020 | 2/27/2020 | P | PASS |
Jack Reynolds
|
|
|
Marco Phone #: ###-#### - R/I ok
|
Rough-in | 2/26/2020 | 2/27/2020 | 2/27/2020 | A | FAIL |
Jack Reynolds
|
|
|
Call half hour before // Marco Phone #: ###-#### - range vent ok b vent ok - need to see 3 exhaust fans added to permit/ a dryer vent added to permit - dryer vent needs proper fittings installed in wall - by final will need to see combustion air opening for mech closet min 100sq" each opening
|
Telephone call | | | 2/27/2020 | | DONE |
|
|
|
Marco Gomez with gomez mechanical adding new fixtures to permit
|
Rough-in | 2/19/2020 | 2/20/2020 | 2/20/2020 | A | FAIL |
Jack Reynolds
|
|
|
call marco 30 minutes before arriving for home access 208 353 5484 thanks Phone #: ###-#### Inspection requested via web by marco gomez - common b vent needs 1" clearances - all bathrooms need exhaust - laundry room needs dryer vent and these items need to be added to permit - will need to see combustion air opening high low for furnace and new location of water heater in basment - 20lb gas pressure test ok
|
Issue PAID IN FULL permit | | | 2/19/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/19/2020 | | DONE |
|
|
|
This permit was created on the web by marco gomez
|