Final | 4/17/2020 | 4/20/2020 | 4/20/2020 | A | PASS |
Brian Scoles
|
|
|
Duct blast report is the the back of the literature rack next to water heater and commission stick is filled out on electrical panel in garage in sharpie Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 4/16/2020 | 4/17/2020 | 4/17/2020 | P | FAIL |
Brian Scoles
|
|
|
2468 re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test needs completed and sticker on electrical panel needs filled out- still smell bit of gas in closet at furnace- replace flex connector with new
|
Final | 4/13/2020 | 4/16/2020 | 4/16/2020 | A | FAIL |
Brian Scoles
|
|
|
2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need approved man j onsite- need 3 screws in b vent to china cap on water heater- duct blast sticker on panel needs filled out completely missing results- smell gas in furnace closet turned off gas valve
|
Pressure Test | 2/25/2020 | 2/26/2020 | 2/26/2020 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart - 5lb flue
|
Rough-in | 2/25/2020 | 2/26/2020 | 2/26/2020 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart
|
Rough-in | 2/24/2020 | 2/25/2020 | 2/25/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- flue at 2.5 psi- metal to plastic connection on exhaust fans need sealed prior to outer insulation- insulation shield in garage needs to go all the way to roof pitch and 1" clearance to insulation shield- left notice on range duct
|
Pressure Test | 2/24/2020 | 2/25/2020 | 2/25/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass tagged meter location- flue at 2.5 psi
|
Issue PAID IN FULL permit | | | 2/24/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/24/2020 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|