Final | 4/29/2020 | 4/29/2020 | 4/29/2020 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- per phone call
|
Final | 4/28/2020 | 4/29/2020 | 4/29/2020 | A | FAIL |
Brian Scoles
|
|
|
Key in lockbox on back electric panel. Home unoccupied Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- no access no lock box found on electrical paned and no code was given- MC cable needs ul approved weather tight fitting at condenser mc cable can not pass thru appliance- is approved man j onsite
|
Final | 3/3/2020 | 3/4/2020 | 3/4/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP 1- need to submit acca report to city of boise for approval/ include erv in crawl with this on how is currently installed 2- need to insulate bare metal supply and return in crawl/ no exposed metal can be showing on taps too 3- need to support ducting in crawl in couple places 4- need to support line set at condenser and uv protect 5- mc cable needs approved ul listed weather tight fitting on condenser mc cable can not just pass thru appliance
left notice kitchen counter- GC onsite too
|
Issue PAID IN FULL permit | | | 3/3/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/3/2020 | | DONE |
|
|
|
This permit was created on the web by Matthew BLANKENSHIP
|