Final | 3/19/2020 | 3/19/2020 | 3/19/2020 | P | FAIL |
Jack Reynolds
|
|
|
Meet Jasper on site. Repairs as per your request have been made.
Jasper - ###-#### - Please give him 30 minutes notice so he can meet you there. Thanks! Phone #: ###-#### Inspection requested via web by Ted Dumont Inc. - A/C still needs fuses - line set insulation needs repaired at indoor coil
|
Final | 3/18/2020 | 3/19/2020 | 3/19/2020 | A | FAIL |
Jack Reynolds
|
|
|
Please contact Jasper 30 minutes prior to your arrival so he could meet you on site. If he misses your call please contact us at ###-####. Phone #: ###-#### Inspection requested via web by Ted Dumont Inc. - A/C needs 35 amp max fuses - b vent needs 1" clearances in attic and garage - insulation shield in garage and attic roof lines - line set and condensate line penetration needs sealed - line set insulation at indoor unit needs repaired
|
Issue PAID IN FULL permit | | | 3/4/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/4/2020 | | DONE |
|
|
|
This permit was created on the web by Ted Dumont Inc.
|