Final | 7/7/2020 | 7/8/2020 | 7/8/2020 | A | PASS |
Jack Reynolds
|
|
|
Call ###-#### for access Phone #: ###-#### Inspection requested via web by Debbie Marino - final ok
|
Conference | 7/1/2020 | 7/2/2020 | 7/2/2020 | A | PASS |
Jack Reynolds
|
|
|
8:30 duct blast Phone #: ###-#### Inspection requested via web by Debbie Marino - duct blast ok
|
Conference | 6/30/2020 | 7/1/2020 | 7/1/2020 | A | NR |
Jack Reynolds
|
|
|
8:30 Duct Blast Phone #: ###-#### Inspection requested via web by Debbie Marino - not ready contractor is sealing leaks in duct work
|
Pressure Test | 4/27/2020 | 4/27/2020 | 4/27/2020 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas ok - tagged meter location
|
Rough-in | 4/27/2020 | 4/27/2020 | 4/27/2020 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - R/I ok - will need to see gas line supported at meter by final
|
Rough-in | 4/21/2020 | 4/22/2020 | 4/22/2020 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas pressure test fail - gas line at meter needs supported - line set arma flex insulation needs repaired in wall 2nd floor - need building inspector's approval for floor joists being cut
|
Pressure Test | 4/21/2020 | 4/22/2020 | 4/22/2020 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - 20lb gas pressure test fail
|
Issue PAID IN FULL permit | | | 4/16/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/16/2020 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|