Permit Information
Permit NumberMEC20-01586
StatusFinaled
Name ANACONDA HEATING
Site Address 5104 W BETHEL ST
Project Name 
Customer Number1234
ePlanReviewNo
Description
Alteration: Installed unit heater and gas pipe to the preasure wash building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/14/20205/14/20205/14/2020APASS
DetailsJack Reynolds
- insulation shield on vent ok
- final ok
Rough-in5/13/20205/14/20205/14/2020APASS
DetailsJack Reynolds
Ive made the correction and need a reinspection Phone #: ###-#### Inspection requested via web by Travis McMillan
- R/I ok
Pressure Test5/14/20205/14/20205/14/2020APASS
DetailsJack Reynolds
Ive made the correction and need a reinspection Phone #: ###-#### Inspection requested via web by Travis McMillan
- 60lb gas test ok
- tagged meter location
Pressure Test4/22/20204/23/20204/23/2020AFAIL
DetailsJack Reynolds
This is a unit heater in a gas pipe job so I need you to expect the rough-in and final for the unit heater and witness the gas pressure which is going to be on 2 p.m. Inspection requested via web by Travis McMillan
- 60lb gas pressure test fail/ All gas lines installed need tested
- gas line at old building front of lot needs supported
- all gas line penentrations through building need protective coating installed
- all appliances needs a shut off valve/ drip leg/ reg/ drip leg installed
-need to see clearnaces on venting for unit heater and pressure washer if combustibles are with in construction of roof
- Permit is on the wrong address and needs adjusted. Should be on 5100 Bethel
Issue PAID IN FULL permit  4/22/2020 DONE
Payment received via Govolutions
Application received  4/22/2020 DONE
This permit was created on the web by Travis McMillan
First Notice5/14/20205/14/2020   
DetailsJack Reynolds