Final | 6/26/2020 | 6/30/2020 | 6/30/2020 | P | PASS |
Jack Reynolds
|
|
|
Homeowner Barbara Lunt ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
Final | 6/18/2020 | 6/18/2020 | 6/18/2020 | P | FAIL |
Jack Reynolds
|
|
|
Homeowner Barbara Lunt ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - furnace venting needs 6" clearances - line set insulation in basement needs repaired and filled in - A/C locking caps - A/C breaker is over sized - Install co sensors near bedrooms
|
Final | 6/10/2020 | 6/15/2020 | 6/15/2020 | P | NH |
Jack Reynolds
|
|
|
Homeowner Barbara Lunt ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - no access to home left notice on front door
|
Issue PAID IN FULL permit | | | 5/6/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/6/2020 | | DONE |
|
|
|
This permit was created on the web by Mary LaFayette
|