Final | 6/8/2020 | 6/9/2020 | 6/9/2020 | A | PASS |
Jack Reynolds
|
|
|
Mechanical Final Inspection needed for Loomis please call Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin - final ok - occ card signed
|
Rough-in | 5/26/2020 | 5/27/2020 | 5/27/2020 | A | FAIL |
Jack Reynolds
|
|
|
Mechanical Rough-In needed for Am please contact Karl with any questions ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin - several locations through out need duct sealed then inspected including bathroom exhaust. After duct seal inspection all new ducts will need to be insulated - several locations need flex ducting supported - one transfer opening still needs core cutting performed on west side of building
|
Rough-in | 5/19/2020 | 5/19/2020 | 5/19/2020 | P | PART |
Jack Reynolds
|
|
|
Mechanical Rough-In needed for Loomis Please contact karl with any questions. Phone #: ###-#### Inspection requested via web by Karl Hestekin - partial R/I only on work area/ vault. Duct seal ok for insulation - will need access to rest of jobsite for rest of R/I - called Karl and left voicemail
|
Issue PAID IN FULL permit | | | 5/19/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/19/2020 | | DONE |
|
|
|
This permit was created on the web by Karl Hestekin
|
First Notice | 6/9/2020 | 6/9/2020 | | | |
Jack Reynolds
|
|
|
|