Rough-in | 6/17/2020 | 6/17/2020 | 6/17/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- R/I ok- 5lb flue pass
|
Rough-in | 6/12/2020 | 6/15/2020 | 6/15/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley 1- need city approved man j onsite 2- 6" fresh air can not tie into R/A can needs tied in near furnace 3- R/A ducting ran between trusses needs insulated to minimum R-6 4- need to fix all rips and tears in arma flex in crawl and near furnace
notice posted front window
|
Pressure Test | 6/12/2020 | 6/15/2020 | 6/15/2020 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
|
Issue PAID IN FULL permit | | | 5/28/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/28/2020 | | DONE |
|
|
|
This permit was created on the web by Terek Worley
|