Rough-in | 6/12/2020 | 6/12/2020 | 6/12/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- units ok to cover- 7800 will need underground gas test completed from meter location to garage to tag meter-
|
Rough-in | 6/11/2020 | 6/12/2020 | 6/12/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- still missing 6" supply tap, duct and register to laundry/utility room- reschedule when ready
|
Rough-in | 6/10/2020 | 6/11/2020 | 6/11/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- still missing supply duct to laundry room in 7800 unit- reinspetion fee issued
|
Rough-in | 6/10/2020 | 6/10/2020 | 6/10/2020 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino - Still need 1" air gap between insulation shield and B-vent on fireplace flue. Missing supply in utility room.
|
Rough-in | 6/9/2020 | 6/10/2020 | 6/10/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- 7822 1- need city approved man j onsite 2- need to firecaulk fireplace flue 3- need lineset box installed exterior of house at condenser location
7800 1- need city approved man j onsite 2- fireplace flue needs leveled off fireplace/ insulation shield needs 1" clearance around pipe/ firestop at attic needs 1" clearance to b vent to wood
left notice front window of unit 7800
|
Pressure Test | 6/10/2020 | 6/10/2020 | 6/10/2020 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- 20lb gas pass units 7800 and 7822 ok to cover- 7800 needs underground tested when installed from meter to house
|
Issue PAID IN FULL permit | | | 6/9/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/9/2020 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|