Rough-in | 6/29/2020 | 6/29/2020 | 6/29/2020 | P | PASS |
Brian Scoles
|
|
|
R/I ok
|
Pressure Test | 6/29/2020 | 6/29/2020 | 6/29/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- 5lb flue pass
|
Rough-in | 6/26/2020 | 6/29/2020 | 6/29/2020 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I will pass when gas test passes gauge wont zero out
|
Pressure Test | 6/26/2020 | 6/29/2020 | 6/29/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gauge wont zero out
|
Rough-in | 6/25/2020 | 6/26/2020 | 6/26/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves 1- need city approved man j onsite 2- gas test flat 3- exhaust fans need sealed where metal ties onto plastic 1st floor 4- 6" fresh air can not tie into R/A can needs tied in near furnace on plenum 5- jump transfer duct in master needs register cans sealed
left notice sliding door
|
Pressure Test | 6/25/2020 | 6/26/2020 | 6/26/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas flat- check gauge to verify zeros out- 5lb flue pass
|
Issue PAID IN FULL permit | | | 6/12/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/12/2020 | | DONE |
|
|
|
This permit was created on the web by Gary Reeves
|