Rough-in | 7/20/2020 | 7/20/2020 | 7/20/2020 | P | PASS |
Brian Scoles
|
|
|
Add p test Phone #: ###-#### Inspection requested via web by Joe Taylor- R/I ok- corrections made
|
Pressure Test | 7/20/2020 | 7/20/2020 | 7/20/2020 | P | PASS |
Brian Scoles
|
|
|
Add rough in Phone #: ###-#### Inspection requested via web by Joe Taylor- 20lb gas pass tagged meter location
|
Pressure Test | 7/16/2020 | 7/17/2020 | 7/17/2020 | A | CANC |
Brian Scoles
|
|
|
Add rough in Phone #: ###-#### Inspection requested via web by Joe Taylor- see note 2 on correction notice
|
Rough-in | 7/16/2020 | 7/17/2020 | 7/17/2020 | A | FAIL |
Brian Scoles
|
|
|
Add P test Phone #: ###-#### Inspection requested via web by Joe Taylor- 1- insulation shield for water heater needs minimum 1" clearance and tabs bent in laying against b vent 2- gas stub out to gas meter needs extended and retest or readjust hanger in wall 3- dryer duct to termination box needs sealed 4- vertical csst gas ping in wall at range shall not be secured to structure shall be free floating 5- need city approved man j onsite for inspection none found 6- dryer duct at ceiling needs notch bigger pipe is deformed needs to maintain round and nail plate installed other side 7- line set needs ran on R/I inspection
left notice front entry window
|
Issue PAID IN FULL permit | | | 7/15/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/15/2020 | | DONE |
|
|
|
This permit was created on the web by Joe Taylor
|