MIS-Aging Inspection | 12/8/2003 | 12/8/2003 | 12/8/2003 | | DONE |
Tom Arcoraci
|
|
|
|
DOC - Permit Finaled | 12/8/2003 | 12/8/2003 | 12/8/2003 | P | PASS |
Tom Arcoraci
|
|
|
Finaled by inspector at 12/8/2003 2:51:12 PM
|
Permanent Occupancy | | 9/20/2002 | 9/20/2002 | | DONE |
|
|
|
|
BLD-Final | 9/20/2002 | 9/20/2002 | 9/20/2002 | A | PASS |
Bob Archibald
|
|
|
Electrical issues ok Per Jim Schmer. OK to issue CO.
|
Permanent occupancy Cert | | | 9/20/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9371 issued 9-20-02 to the Mountain View Professional Building.
|
BLD-Final | 9/17/2002 | 9/17/2002 | 9/17/2002 | P | PART |
Bob Archibald
|
|
|
Structural Corrections made ok. Code enforcement, Fire and plumbing issues made ok. Waiting on confermation of electrical.
|
FIR-Final | 8/6/2002 | 8/7/2002 | 8/7/2002 | A | FAIL |
Troy Cobbley
|
|
|
the fire alarm system for this building is not required and the existing system is not correct for current code. I left the owners with the option to upgrade the fire alarm system or to remove the existing system 8/7/2002 11:56:51 AM
|
Override - Parcel Holds | | | 8/6/2002 | | |
|
|
|
|
Conference | 8/5/2002 | 8/5/2002 | 8/5/2002 | | PART |
Bob Archibald
|
|
|
Site visit with Lee, Jim and Carol. CN'S issued by electrical, plumbing and myself. Instructed Bob to contact me for reinspection when items complete.
|
Miscellaneous action | | | 3/4/2002 | | PART |
Bob Archibald
|
|
|
Site visit by myself and JG with Bob and Michelle to review list of requirements and corrections needed.
|
COD-Conference | 2/14/2002 | 2/14/2002 | 2/14/2002 | P | PART |
Bob Archibald
|
|
|
Observations based on requirements of resolution 13533.
A. Exterior exit doors require removal of thumb turn locking hardware and need to open in the direction of travel
B. Exit signage requires maintenance and relocation for visibility from any location.
C. Stairways with 2 or more risers require hand rails.
D. Conference room and offices located in basement do not meet required egress or natural light requirements.
E. Corridor system has a dead end configuration exceeding 20 feet.
F. Fire alarm system requires testing.
G. Electrical system requires review, multiple circuts observed.
H. Leaky plumbing observed in basement utility room.
|
Application received | | | 2/14/2002 | | |
|
|
|
|
Plan Reviewer's Copy of Permit | | | 2/14/2002 | | DONE |
|
|
|
|
Permit taken to Permit Desk | | | 2/14/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 2/14/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 2/14/2002 | | |
|
|
|
|
Issue Misc Permit............ | | | 2/14/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 2/14/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|