Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberMIS02-00025
StatusFinaled
Name BOB COOK
Site Address 2309 N MOUNTAIN VIEW DR
Project Name 
Customer Number 
ePlanReview 
Description
**(Inspection Request)** This permit has been requested by Bob Cook for a propriety inspection of this existing office. Inspector to review office builidng onsite to determine if there are any code related requirements that need to be addressed. Reserch of building department permits indicate that remodels were performed on an B-2 occupancy / Building type VN / Land Use Zone R-1c/ Date 4/25/79. No Square footage was mentioned, no avalible floor plans to reference. NO WORK IS AUTHORIZED UNDER THIS PERMIT (rmh)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection12/8/200312/8/200312/8/2003 DONE
DetailsTom Arcoraci
DOC - Permit Finaled12/8/200312/8/200312/8/2003PPASS
DetailsTom Arcoraci
Finaled by inspector at 12/8/2003 2:51:12 PM
Permanent Occupancy 9/20/20029/20/2002 DONE
Details
BLD-Final9/20/20029/20/20029/20/2002APASS
DetailsBob Archibald
Electrical issues ok Per Jim Schmer. OK to issue CO.
Permanent occupancy Cert  9/20/2002 DONE
Perm. Occ. Cert. #9371 issued 9-20-02 to the Mountain View Professional Building.
BLD-Final9/17/20029/17/20029/17/2002PPART
DetailsBob Archibald
Structural Corrections made ok. Code enforcement, Fire and plumbing issues made ok. Waiting on confermation of electrical.
FIR-Final8/6/20028/7/20028/7/2002AFAIL
DetailsTroy Cobbley
the fire alarm system for this building is not required and the existing system is not correct for current code. I left the owners with the option to upgrade the fire alarm system or to remove the existing system 8/7/2002 11:56:51 AM
Override - Parcel Holds  8/6/2002  
Conference8/5/20028/5/20028/5/2002 PART
DetailsBob Archibald
Site visit with Lee, Jim and Carol. CN'S issued by electrical, plumbing and myself. Instructed Bob to contact me for reinspection when items complete.
Miscellaneous action  3/4/2002 PART
DetailsBob Archibald
Site visit by myself and JG with Bob and Michelle to review list of requirements and corrections needed.
COD-Conference2/14/20022/14/20022/14/2002PPART
DetailsBob Archibald
Observations based on requirements of resolution 13533.
A. Exterior exit doors require removal of thumb turn locking hardware and need to open in the direction of travel
B. Exit signage requires maintenance and relocation for visibility from any location.
C. Stairways with 2 or more risers require hand rails.
D. Conference room and offices located in basement do not meet required egress or natural light requirements.
E. Corridor system has a dead end configuration exceeding 20 feet.
F. Fire alarm system requires testing.
G. Electrical system requires review, multiple circuts observed.
H. Leaky plumbing observed in basement utility room.


Application received  2/14/2002  
Plan Reviewer's Copy of Permit  2/14/2002 DONE
Permit taken to Permit Desk  2/14/2002 DONE
Inspection Record Card- Bld  2/14/2002  
Override - Parcel Holds  2/14/2002  
Issue Misc Permit............  2/14/2002  
Override - Parcel Holds  2/14/2002  
Case Summary    DONE
Case Summary    DONE