MIS-Aging Inspection | 5/2/2005 | 5/2/2005 | 5/2/2005 | | PASS |
Jim Storey
|
|
|
russ aproved
|
DOC - Permit Finaled | 5/2/2005 | 5/2/2005 | 5/2/2005 | P | PASS |
Jim Storey
|
|
|
russ aproved
|
FIR-Final | 2/18/2004 | 2/18/2004 | 2/18/2004 | A | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
MIS-Aging Inspection | 1/26/2004 | 1/26/2004 | 1/26/2004 | | CANC |
Russ Owen
|
|
|
No action on this after fire life safety left 5 day notice. 1/27/2004 11:52:03 AM
|
FIR-Conference | 10/14/2003 | 10/14/2003 | 10/14/2003 | A | DONE |
Troy Cobbley
|
|
|
I left a 5 day notice with the owner of the store. I went over fire life safety deficiencies with him in the store, and his wife over the phone, and explained what needed to be done to get their occupancy permit.
|
MIS-Aging Inspection | 9/18/2003 | 9/18/2003 | 9/18/2003 | | CANC |
Russ Owen
|
|
|
no inspection called for 9/24/2003 6:21:50 PM
|
Issue Misc Permit............ | | | 5/23/2003 | | DONE |
|
|
|
|
FIR-Final | 3/21/2003 | 3/24/2003 | 3/24/2003 | A | FAIL |
Troy Cobbley
|
|
|
###-#### call to meet there. Sprinkler pendants in the middle room are overspace as well as possible the pendant in the office. Per Bill Alexander max sprinkler head spacing is 120 sq. ft.. The existing sprinkler hangers do not meet code and will need upgraded. Repair the exit signs. Provide one fire extinguisher. 3/24/2003 10:48:55 AM
|
BLD-Final | 3/21/2003 | 3/24/2003 | 3/24/2003 | P | PART |
Russ Owen
|
|
|
###-#### call first to meet there. Appears ok no changes noted, would need exit signed repaired,also fire /life safety. 3/25/2003 10:13:44 AM
|
Application received | | | 3/21/2003 | | |
|
|
|
|
Case Summary | | | 3/21/2003 | | DONE |
|
|
|
|
Permit taken to Permit Desk | | | 3/21/2003 | | DONE |
|
|
|
|
Plans taken to the Permit Desk | | | 3/21/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/21/2003 | | |
|
|
|
|
Telephone call | | | 3/21/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Issue Misc Permit............ | | | 3/21/2003 | | DONE |
|
|
|
|