Final Permit | | | 3/12/2004 | | DONE |
|
|
|
BLD03-02360 issued to replace mis. permit & issued perm. occ. cert.
|
FIR-Final | 9/26/2003 | 9/29/2003 | 9/29/2003 | A | PART |
Rick Jackson
|
|
|
kevin ###-#### canopies for fire sprinklers and head overspaced by water heater in restroom area; hang extinguisher with current tag; needs emergency lighting (2 exits required) and exit signs to operate on battery power 9/29/2003 12:46:33 PM
|
BLD-Final | 9/26/2003 | 9/29/2003 | 9/29/2003 | P | PART |
Jim Sly
|
|
|
###-#### kevin No structural corrections.....Need fire and structural approval for Perm. Occ. status within 90 days of this notice. OK for Temp Occ.
9/29/2003 12:07:41 PM 9/29/2003 12:08:15 PM
|
Temporary occupancy cert | | | 9/29/2003 | | DONE |
|
|
|
Temp. Occ. Cert. #5003 issued 9-29-03 to Treasure Valley Paper, Inc.
|
Case Summary | | | 9/26/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/26/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/26/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/26/2003 | | DONE |
|
|
|
Left message for Kevin that permit is ready & fees
|
Issue Misc Permit............ | | | 9/26/2003 | | DONE |
|
|
|
|
Application received | | | 9/25/2003 | | |
|
|
|
|