Case Summary | | | 6/4/2010 | | DONE |
|
|
|
|
Case Summary | | | 4/14/2010 | | |
|
|
|
|
Reprint Misc Permit..... | | | 4/14/2010 | | DONE |
|
|
|
|
MIS-Aging Inspection | 1/23/2006 | 1/23/2006 | 1/23/2006 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Finaled | 1/23/2006 | 1/23/2006 | 1/23/2006 | P | PASS |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 11/21/2005 | 11/21/2005 | 11/21/2005 | | NR |
Tom Arcoraci
|
|
|
|
MIS-Aging Inspection | 9/21/2005 | 9/21/2005 | 9/21/2005 | | PASS |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 7/22/2005 | 7/22/2005 | 7/25/2005 | | PASS |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 5/16/2005 | 5/16/2005 | 5/16/2005 | | PASS |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 3/14/2005 | 3/14/2005 | 3/14/2005 | | CANC |
Troy James
|
|
|
|
FIR-Final | 11/9/2004 | 11/9/2004 | 11/9/2004 | P | PASS |
Rick Jackson
|
|
|
|
BLD-Final | 11/9/2004 | 11/9/2004 | 11/9/2004 | P | PASS |
Dave Hannah
|
|
|
ok for perm occ 11/9/2004 4:03:34 PM
|
MIS-Aging Inspection | 10/7/2004 | 10/7/2004 | 10/13/2004 | | PASS |
Rick Jackson
|
|
|
The item holding signing this off is the extinguishing system hood as the lights don't shut off upon activation; talked to Mike of General Fire and he has talked to the electrical contractor and the lights will be disconnected and then he will call for a final on the hood permit 10/13/2004 8:29:19 AM
|
MIS-Aging Inspection | 7/26/2004 | 7/26/2004 | 7/26/2004 | | DONE |
Troy James
|
|
|
Informed owner to finish fire inspection and call for final structural. 7/30/2004 11:29:49 AM
|
BLD-Conference | 5/18/2004 | 5/18/2004 | 5/18/2004 | P | DONE |
Dave Hannah
|
|
|
talked with manager he will schedule inspections say all c/n items are complete 5/18/2004 1:56:33 PM
|
MIS-Aging Inspection | 5/12/2004 | 5/12/2004 | 5/12/2004 | | FAIL |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 2/11/2004 | 2/11/2004 | 2/11/2004 | | DONE |
Dave Hannah
|
|
|
wip 2/11/2004 9:37:01 AM
|
FIR-Final | 11/14/2003 | 11/14/2003 | 11/14/2003 | P | FAIL |
Rick Jackson
|
|
|
###-#### ###-#### max occupant load sign; extinguishers needed; repair exit signs; add emergency light at main exit area; trip test the extinguishing system; "Door to remain... " sign at main exit door 11/14/2003 1:38:41 PM
|
BLD-Final | 11/14/2003 | 11/14/2003 | 11/14/2003 | P | FAIL |
Dave Hannah
|
|
|
###-#### ###-#### Max needs fire life safety sign off on c/n items ok after that 11/14/2003 2:32:18 PM
|
Print Occupancy Form | | | 11/14/2003 | | DONE |
|
|
|
|
Telephone call | | | 11/14/2003 | | DONE |
|
|
|
called left message for max that permit is ready & fee given///dld 11-14-03 8:51 am
|
Issue Misc Permit............ | | | 11/14/2003 | | DONE |
|
|
|
|
Application received | | | 11/13/2003 | | |
|
|
|
|
Meeting | | | 11/13/2003 | | DONE |
|
|
|
Met with tenant rep. He provided a copy of their menu but did not have approval from CDH. I gave him a copy of the plan to take to CDH for approval signature and date.
|
Meeting | | | 11/13/2003 | | DONE |
|
|
|
Met with Louise Waldorf, PW and reviewed the scope of the project. the kitchen will stay as approved in the past and I left the copy of the menu with her to review with Bev Dugger.
|
Meeting | | | 11/13/2003 | | DONE |
|
|
|
Louise Waldorf brought the plans back to me. The Interlude Bar & Grill was originally rated as a full service restaurant and since the only change was the opening between the two tenant spaces, there would be no additional fee's.
|
Meeting | | | 11/13/2003 | | DONE |
|
|
|
Max Mohammadi, partner in OPA brought back a copy of the flor plan signed by Bob Jue noting the new 5 ft. opening. Bob requested that the occupancy approval sign be posted at the site for his inspector, Bud Fulleton to sign off on when he made the field inspection for CDH.
|
Plan Reviewer's activity | | | 11/13/2003 | | DONE |
|
|
|
Combined copies of past plans from records to show the site plan, floor plan and indicated location of new opening by tenant. Attached application for occupancy approval review and created permit for inspections.
|
Plan Reviewer's Copy of Permit | | | 11/13/2003 | | |
|
|
|
|
Case Summary | | | 11/13/2003 | | |
|
|
|
|
Meeting | | | 11/10/2003 | | DONE |
|
|
|
Met with tenants representative to review proposal. Tenant has already made opening between Cazba II & "OPA" for ease of interaction between two spaces. Both spaces are under the management of the same company but each will function separately with own C.O and kitchen / dining areas, exits, etc. We verified from plans on file that the wall penetrated was nonbearing. Instructed tenant that he needed to obtain approval of the tenant use from Central district Health and I needed to know the status of the kitchen and what their menu would be for Public Works.
|