MIS-Aging Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 | | DONE |
Jim Sly
|
|
|
EXP. No Bible group located in this Bldg. 5/20/2005 4:25:37 PM
|
DOC - Permit Expired | 5/20/2005 | 5/20/2005 | 5/20/2005 | P | PASS |
Jim Sly
|
|
|
Expired by inspector at 5/20/2005 4:25:44 PM
|
FIR-Final | 3/25/2004 | 3/25/2004 | 3/25/2004 | P | PASS |
Rick Jackson
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Final | 3/24/2004 | 3/24/2004 | 3/24/2004 | P | PART |
Russ Owen
|
|
|
MATT #120; Phone #: ###-#### Internet Inspection Request from: Darla Downs This still needs fire/life safety. 3/23/2004 11:40:50 PM
|
FIR-Final | 3/24/2004 | 3/24/2004 | 3/24/2004 | P | FAIL |
Rick Jackson
|
|
|
Is having BLD final this afternoon as well. Matt; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes The fire alarm panel is still in trouble with a duct detector in Fiber Pipe 3/24/2004 3:25:10 PM
|
FIR-Final | 1/15/2004 | 1/16/2004 | 1/16/2004 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given. The tenant needs to re-install the canopy on one sprinkler pendant that has fallen off. Also one of the duct smoke detectors in this tenant space is in alarm/supervisory. The remote LED is lit up. The fire alarm panel is in trouble. This will need to be fixed prior to receiving a permanant occupancy. Correction notice was left with tenant representative. 1/16/2004 10:22:28 AM
|
BLD-Final | 1/15/2004 | 1/16/2004 | 1/16/2004 | A | PART |
Jim Sly
|
|
|
Michael; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes OK for Temp Occ. C/N obtain Perm Occ. status from both Fire and Structural within 90 days of this notice. OK for Perm when Perm Occ for fire approved. :) 1/16/2004 11:52:44 AM 1/16/2004 11:52:54 AM 1/16/2004 11:55:07 AM 1/16/2004 11:55:36 AM
|
Temporary occupancy cert | | | 1/16/2004 | | DONE |
|
|
|
Temp. Occ. Cert. # 5066 issued 1-16-04 to Faith Community Bible Church.
|
Inspection Record Card- Bld | | | 1/15/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/15/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/15/2004 | | DONE |
|
|
|
left message for Mike --- permit is ready.
|
Print Occupancy Form | | | 1/15/2004 | | DONE |
|
|
|
|
Print Occupancy Form | | | 1/15/2004 | | DONE |
|
|
|
|
Issue Misc Permit............ | | | 1/15/2004 | | DONE |
|
|
|
|
Application received | | | 1/14/2004 | | |
|
|
|
|
Miscellaneous action | | | 1/14/2004 | | PASS |
|
|
|
This is permit is to approved for temporary occupancy until May of 2004.
|
Plan Reviewer's Copy of Permit | | | 1/14/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/14/2004 | | DONE |
|
|
|
|