Permanent occupancy Cert | | | 9/29/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10315 issued 9-29-04 to Timbercreek Cabinetry.
|
MIS-Aging Inspection | 6/9/2004 | 6/9/2004 | 6/9/2004 | | CANC |
Tom Arcoraci
|
|
|
|
DOC - Permit Expired | 6/9/2004 | 6/9/2004 | 6/9/2004 | A | PASS |
Tom Arcoraci
|
|
|
Expired by inspector at 6/9/2004 9:58:25 AM
|
BLD-Final | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | PASS |
Troy James
|
|
|
clay ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR-Final | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 4/9/2004 8:55:46 AM
|
Permanent Occupancy | | 4/9/2004 | 4/9/2004 | | DONE |
|
|
|
|
FIR-Final | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | FAIL |
Troy Cobbley
|
|
|
Provide verification of annual inspection for the fire alarm system. Provide covers on the electrical outlets that are missing. Remove thumbturn on east exit door. Provide fire extinguisher on the second floor. Remove emergency lights that don't work. 4/7/2004 2:25:29 PM
|
BLD-Final | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | CANC |
Russ Owen
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR-Final | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | FAIL |
Troy Cobbley
|
|
|
Repair exit signs. Remove thumb turns on the south and the east facing exterior doors. Provide automatic flush bolts on the main entry exit. Provide approved door hardware on the east side double doors. Provide verification on the annual inspection for the fire alarm. Provide dedicated circuit for the fire alarm panel (it appears to be on a light circuit) Lower the fire extinguisher in the riser room to 48" from finish floor to handle. Repair and test emergency lights. Repair the toilet leak. Provide covers on the electrical outlets that have been damaged. Pendant head at the base of the south stairs is obstructed by a light fixture which actually covers part of the eschouseon. Provide emergency light in stairwell. Provide permit paper work so a complete inspection can be performed. 2/25/2004 9:55:03 AM
|
BLD-Final | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | CANC |
Russ Owen
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Annette Moore Needs fire /life safety 2/24/2004 8:37:53 PM
|
Issue Misc Permit............ | | | 2/24/2004 | | DONE |
|
|
|
|
Application received | | | 2/23/2004 | | |
|
|
|
|
Case Summary | | | 2/23/2004 | | DONE |
|
|
|
|
Permit taken to Permit Desk | | | 2/23/2004 | | DONE |
|
|
|
|
Plans taken to the Permit Desk | | | 2/23/2004 | | |
|
|
|
|
Inspection Record Card- Bld | | | 2/23/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/23/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/23/2004 | | DONE |
|
|
|
spoke with Jeff Reed -- permit is ready.
|