MIS-Aging Inspection | 1/9/2006 | 1/9/2006 | 1/11/2006 | | PASS |
Jim Storey
|
|
|
doc expired
|
DOC - Permit Expired | 1/11/2006 | 1/11/2006 | 1/11/2006 | P | PASS |
Jim Storey
|
|
|
|
MIS-Aging Inspection | 11/8/2005 | 11/8/2005 | 11/8/2005 | | DEFR |
Jim Storey
|
|
|
to gs
|
Issue Sewer Permit | | | 11/7/2005 | | |
|
|
|
|
Case Summary | | | 8/10/2004 | | |
|
|
|
|
Permanent Occupancy | | 6/2/2004 | 6/2/2004 | | DONE |
|
|
|
|
Permanent Occupancy | | 6/2/2004 | 6/2/2004 | | DONE |
|
|
|
|
BLD-Final | 6/1/2004 | 6/2/2004 | 6/2/2004 | A | PASS |
Jim Storey
|
|
|
DUANE MARLER PLEASE CALL 1ST FOR ACCESS; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
DOC - Permit Finaled | 6/2/2004 | 6/2/2004 | 6/2/2004 | A | PASS |
Jim Storey
|
|
|
Finaled by inspector at 6/2/2004 10:08:32 AM
|
Permanent occupancy Cert | | | 6/2/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10175 issued 6-2-04 to the Airport Maintenance Building.
|
BLD-Final | 5/17/2004 | 5/18/2004 | 5/18/2004 | A | CANC |
Jim Storey
|
|
|
call 1st for access-duane marler ###-####
|
FIR-Final | 5/17/2004 | 5/18/2004 | 5/18/2004 | A | FAIL |
Rick Jackson
|
|
|
duane marler ###-#### --call 1st before insp for access Need exit signs at two designated exits in warehouse and emergency lighting; extinguishers need certification; keyed main exit in office door; landing at northeast warehouse exit; sign above main exit in office 5/18/2004 2:42:24 PM
|
BLD-Conference | 5/17/2004 | 5/18/2004 | 5/18/2004 | P | FAIL |
Jim Storey
|
|
|
needto meet rick and dewyane with key 1:30 pm smoke seals / exit hardware /front door signage and keyed dead bolt/ fire extingsers/min. for temp occ. 5/18/2004 2:30:59 PM
|
Issue Misc Permit............ | | | 5/17/2004 | | DONE |
|
|
|
|
Plan Reviewer's activity | | | 5/14/2004 | | DONE |
|
|
|
This building was originally constructed for Chem Lawn as office / parking / storage facility in 1984, BLD1015222 and appears to have been finaled by plumbing & structural in July & August of 1984. No certificate of occupancy was issued and the facility has been occupied as recent as November 2002 by Treasure Valley Beverage, per report from Duane Marler, Airport Project Manager.
The building was to be constructed wiothout any wood inside or out to comply with construction type II-N for area of the building. this was noted on the approved plans by use of the plan review comments. Approved plans were not used to constrct by or the plans were ignored by involved parties, but in any case the wood was used within the structure. This building as-built, would have been classified as type V-N under the 1979 UBC and require sprinkler system for allowable area increase or use of a 2-hour Area Separation Wall constructed to create two buildings within the maximum allowable square footage of an area being 16,000 sq. ft. Under the 2000 IBC, the building would require a sprinkler system throughout or use of fire-walls to divide into fire areas of approximately 14,000 sq. ft. or less by 3-hour wall construction.
Airport Project manager provide copies of original plans from records but they had not copied the permit or plan review report requirements recorded as part of and with the original plans. I faxed a copy of this information to Duane Marler. Also received an application for inspection to determine requirements for issuance of a C.O. per Resolution 13533. Inspectors will determine what is required to obtain a C.O. per the Resolution. Copy of file to Jim Storey with discussion on circumstances and copy to Rick Jackson out box for his reference.
|
Permit taken to Permit Desk | | | 5/14/2004 | | PASS |
|
|
|
Per Resolution 13533.
|
Plans taken to the Permit Desk | | | 5/14/2004 | | PASS |
|
|
|
Per Resolution 13533.
|
Permit Ready to Issue | | | 5/14/2004 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/14/2004 | | DONE |
|
|
|
|
Telephone call | | | 5/14/2004 | | |
|
|
|
spoke with Duance -- permit is ready.
|
Application received | | | 5/13/2004 | | |
|
|
|
|
Meeting | | | 5/11/2004 | | DONE |
|
|
|
Duane Marler has met with Carl Westfall, plan reviewer, to discuss the data he had found concerning the project at 4663 Enterprise. Mr. Marler has proceeded with the MIS Application per Resolution 13533, proposing to occupy the existing building for uses originally approved. Mr. Marler had had Olson & Associates architects perform an imminent hazards walk through evaluation using the data on the back of the application form. I have attached a copy of Mr. Marler's submitted information for use by the inspection team.
|