MIS-Aging Inspection | 3/9/2009 | 3/9/2009 | 3/9/2009 | | PASS |
Tom Arcoraci
|
|
|
|
DOC - Permit Finaled | 3/9/2009 | 3/9/2009 | 3/9/2009 | P | PASS |
Tom Arcoraci
|
|
|
|
MIS-Aging Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 | | NR |
Tom Arcoraci
|
|
|
|
MIS-Aging Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 | | PASS |
Tom Arcoraci
|
|
|
|
FIR-Final | 8/21/2008 | 8/21/2008 | 8/21/2008 | P | PASS |
Troy Cobbley
|
|
|
life safety passed.
|
FIR-Final | 8/11/2008 | 8/12/2008 | 8/12/2008 | A | FAIL |
Troy Cobbley
|
|
|
Provide signage at the secondary containment control valve that indicates "This valve to be normally closed at all times". I spoke to Bill about this via telephone. All other items are ok
|
BLD-Final | 7/28/2008 | 7/29/2008 | 7/29/2008 | A | DEFR |
Tom Arcoraci
|
|
|
bill Freeman Phone #: ###-#### 3684 needs fire only
|
MIS-Request for Extension | 6/10/2008 | 6/10/2008 | 6/10/2008 | A | PASS |
Tom Arcoraci
|
|
|
|
Reprint Misc Permit..... | | | 6/10/2008 | | DONE |
|
|
|
|
Case Summary | | | 6/10/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (I) | | | 6/10/2008 | | DONE |
Tisha Gallop
|
|
|
reopen permit per Tom A.
|
MIS-Aging Inspection | 2/11/2008 | 2/11/2008 | 2/11/2008 | | NR |
Tom Arcoraci
|
|
|
|
DOC - Permit Expired | 2/11/2008 | 2/11/2008 | 2/11/2008 | A | PASS |
Tom Arcoraci
|
|
|
|
Telephone call | | | 12/17/2007 | | DONE |
|
|
|
Telcon with Bill Freeman, ###-#### ext 3684. The contracts for the recently approved modified design have been let but the contractor is not able to start the project for another 4 months. Therefore, there will continue to be no activity on this permit for that time. I told him the permit will now remain active for another 6 months from when we re--issued the modified plans; he indicated they expect to have construction underway within that time-period.
|
Issue permit | | | 12/14/2007 | | DONE |
|
|
|
|
MIS-Aging Inspection | 12/3/2007 | 12/3/2007 | 12/10/2007 | | CANC |
Tom Arcoraci
|
|
|
|
DOC - Permit Expired | 12/10/2007 | 12/10/2007 | 12/10/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
Plan Reviewer's activity | | | 11/15/2007 | | PASS |
|
|
|
Plans approved. Taken to Rita for re-issuing.
|
Case Summary | | | 11/15/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/13/2007 | | DONE |
|
|
|
Telcon with Will Winslow who confirmed he accepted a high level "alarm" as acceptable for "control" considering the arrangement and circumstances of this particular installation.
|
Plan Reviewer's activity | | | 10/30/2007 | | PEND |
|
|
|
Plans reviewed and found acceptable except for question on use of a liquid level alarm in lieu of a level control. Left voice message with Will Winslow to discuss.
|
Miscellaneous action | | | 10/29/2007 | | DONE |
|
|
|
Received requested calculations and 2nd set of plans from Bill Freeman.
|
Application received | | | 10/25/2007 | | |
|
|
|
New Plans submitted reflecting a new design.
|
Plan Reviewer's activity | | | 10/25/2007 | | FAIL |
|
|
|
Email sent to Bill Freeman:
1. Provide two sets of plans. One to be issued to you and one to be retained for City Records. (Only one set was provided)
2. Provide calculations (two sets)verifying the containment volume capacity is at least equal to the tank volume plus the volume of a 24-hour rainfall based on a 25-year storm.
3. Add plan details showing an automatic liquid level limit control to prevent overfilling of the tank. (IFC 2703.2.7)
4. Provide a tank specific data sheet or tank-specific information indicating actual volume capacity and chemical resistance. (The tank information sheet provided is only an ordering guide. This information may be provided to the inspector at time of inspection if desired)
|
MIS-Aging Inspection | 10/3/2007 | 10/3/2007 | 10/3/2007 | | NR |
Tom Arcoraci
|
|
|
fire only exp on 10-31-07
|
MIS-Aging Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 | | NR |
Tom Arcoraci
|
|
|
|
Reprint Sewer Permit Public/wk | | | 8/2/2007 | | |
|
|
|
|
Plan Reviewer's activity | | | 5/4/2007 | | PASS |
|
|
|
Plans reviewed and approved by outside Haz Mat consultant, Wil Winslow, as drawn, subject to satisfactory inspection verifying compliance with the Plan Review Checklist provided by the reviewer. Final inspection to be performed by PDS/Fire.
|
Permit Ready to Issue | | | 5/4/2007 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/4/2007 | | |
|
|
|
|
Print Occupancy Form | | | 5/4/2007 | | DONE |
|
|
|
|
Issue Misc Permit............ | | | 5/4/2007 | | DONE |
|
|
|
|
Application received | | | 4/24/2007 | | |
|
|
|
|