Final Permit | | | 2/18/2008 | | DONE |
|
|
|
|
DOC - Permit Finaled | | | 2/18/2008 | | DONE |
|
|
|
|
FIR-Final | 2/15/2008 | 2/15/2008 | 2/15/2008 | P | PASS |
Sam Rogers
|
|
|
Corrections from last inspection made satisfactorily.
|
FIR-Final | | 1/31/2008 | 1/31/2008 | P | FAIL |
|
|
|
Conducted inspection to verify cabinet compliance with IFC 2006, 1805.2.3.5. Pressure monitor and flow switch alarm (item 3.2) and supply valve shut off (item 5) were not tested as the system was in operation and would have disrupted critical processes; accepted several employees' statements attesting it had been tested and verified prior to commissioning and was in their written test records. All other requirements appeared to be in compliance except the "door open" local audible alarm. The sounder was found to be defective. Will follow up at next site visit.
|
MIS-Aging Inspection | 1/17/2008 | 1/17/2008 | 1/17/2008 | | PASS |
Jim Storey
|
|
|
paul following up as to where we are in the progration of instaltion.
|
Permit Ready to Issue | | | 10/18/2007 | | DONE |
|
|
|
|
Issue permit | | | 10/18/2007 | | DONE |
|
|
|
|
Staff review | | | 10/11/2007 | | PASS |
|
|
|
Dave Hanneman approved the use of this cabinet as supplied, including detection and vermiculite in the base, as acceptable to comply with IFC 2006, Table 1805.2.2 (d)(g) for storage of pyrophoric liquid (TMA ) up to 5.3 gal's max.
|
Miscellaneous action | | | 9/28/2007 | | DONE |
|
|
|
Received cover letter from Paul Marcolina with an attached letter from Air Products and Chemicals verifying they market the cabinet for the intended use and providing supporting information for their position that the cabinet meets the intent of IFC requirements, including an automatic fire suppression system.
|
Telephone call | | | 9/20/2007 | | DONE |
|
|
|
telcons from Chris Jaeger Prod Mgr and Eugene Nye, Product Safety Group, Chem Gard/Air Products in response to my online-request for information regarding fire suppression. They indicate they feel the cabinet is suitable for TMA without further fire suppression. They will send a letter elaborating on supporting details to Bobbie Smith at Micron which Micron can submit in response to the Fire Marshal's request. They expect the letter will arrive on Monday, 9/24.
|
Application received | | | 9/14/2007 | | DONE |
|
|
|
Meeting and D. Hanneman, S. Rogers to discuss Micron's proposal. Dave requested they provide manufacturer's statement that the proposed cabinet with vermiculite in the base and UV/IR/heat detection constitutues an "automatic fire extinguishing/suppression system in accordance with Chapter 9" as required by IFC table 1805.2.1; or verification by an outside design professional that the proposed cabinet design constitutes an acceptable alternative to the required fire protection. Micron agreed to obtain and resubmit. At the end of the meeting, Bobbie refered to a position paper from the manufacturer dated June 15, 2007, which was not not previously submitted; a copy was left with us.
|
Case Summary | | | 9/14/2007 | | DONE |
|
|
|
|
Meeting | | | 8/23/2007 | | DONE |
|
|
|
Meeting at city hall with J. Velikoff, P. Marcolina and Tom Roberts of Micron, J. Gilliland, S. Rogers to discuss Micron's proposal. No new information provided. Requested they provide manufacturer's statement that the proposed cabinet with vermiculite in the base and UV/IR/heat detection constitutues an "automatic fire extinguishing/suppression system in accordance with Chapter 9" as required by IFC tatle 1805.2.1; or approval/certification by an approved testing lab verifying the proposed cabinet design constitutes an acceptable alternative to the required fire protection. Micron to reschedule another meeting when info is ready and present it to Dave Hanneman for review.
|
Case Summary | | | 8/20/2007 | | |
|
|
|
|
Meeting | | | 8/9/2007 | | DONE |
|
|
|
Onsite meeting with facility engineers. I explained my concerns with the resubmitted information; they provided additional clarification but no further documentation. I requested they provide additional information, including a specific plan of Micron's proposed design, the length and slope of the tubes connecting the cabinet to workstations, a clear manufacturer's statement indicating the proposed cabinet is intended to be used without a further fire protection system; the full laboratory test report (rather than just the power point slides), any third-party technical opinions of the test results and the testing lab's protocol; and if available, the results of any tests done on the proposed cabinet with full containers of TMA spilled within the cabinet. I explained this information would be subject to further consideration by the Fire Official and Building Official, and it would probably require technical assistance and an outside technical opinion, in accordance with IFC104.7.2 and 104.9.
I explained that my principle concern is the lack of an "approval", or "listing" by a testing laboratory or even a statement by the manufacturer indicating that the cabinet arrangement has been verified to be an equivalent alternative to the Code required "fire protection system". Another concern is the lack of a plan of Micron's proposed installation to compare to the test set-up. Concerns with the test information provided include: lack of information on the name and credentials of the testing laboratory; the limited information provided by the Power Point slides instead of a complete test report; the test protocol uses isododecane instead of TMA in the bulk canister ("to provide a safe testing apparatus"); the test protocol uses only 148 grams of TMA (equivalent volume of one, ΒΌ" line of 56.9 ft length) rather than to spill of one of the two 2-liter canisters which are intended to be stored in the cabinet; there is conflicting information on the weight and volume of vermiculite used; the obvious differences in comparing the use of vermiculite to "over-packing" TMA canisters during shipment and the proposed cabinet arrangement in which the vermiculite material is approximately 5' below the TMA canisters.
The 2006 Fire Code requires the cabinet to be "internally protected with an approved, automatic fire-extinguishing or suppression ("fire protection" per 2006) system complying with Chapter 9". In the proposed arrangement, vermiculite material, which is supposed to act as the fire protection agent, is located at the bottom of the cabinet. The Power Point slide indicates "the bulk of the TMA will burn before it hits vermiculite" (page 4) and "the bags were melted by the burning TMA" (P 12). This indicates to me that the fire protection affect of the vermiculite was minimal based on the amount of TMA that burned before hitting the vermiculite. Perhaps the vermiculite would have more of an effect in a larger spill, but that scenario was not tested according to the information provided.
|
Staff review | | | 8/8/2007 | | DONE |
|
|
|
reviewed resubmitted information. Resubmittal included generic information on control of metalorganic fires; MSDS for TMA, manufacturer's instructions for infra-red detectors and for smoke detectors, an installation and operation manual for the Schumacher ChemGuard Delivery System, portions of a Powerpint presentation by Air Products entitled TMA ChemGuard 400 Test Results, and a CG400 Response Alarm matrix. The manufacturer's information provided (ref paragraph 5.1) does not mention a built-in fire protection system or the use of vermiculite as an alterntive to such protection. The Powerpoint information provided is insufficient to understand the specific design concepts and does not indicate an "approval" of the cabinet with vermiculite fill as an equivalent alternative protection system.
|
Miscellaneous action | | | 8/6/2007 | | DONE |
|
|
|
Received 2nd letter and additiaonl information from Micron. Copy attached
|
Meeting | | | 7/19/2007 | | DONE |
|
|
|
Discussed initial letter on site. Letter provides insufficient information to understand the concept or specifics of the alternative design proposal. Need documentation from manufacturer showing that the proposed cabinet with vermiculite has been tested and "approved" by an acceptable testing laboratory as an acceptable alternative to "a fire protection system" for this intended application and sufficient specific detailed information of the proposed installation to show the proposed design is within the manufacturer's and the approval agency's parameters. This additional information will then be further reviewed by the Fire and Building officials.
|
Staff review | | | 7/16/2007 | | DONE |
|
|
|
Reviewed initial letter. Letter provides insufficient information to understand the concept or the alternative design proposal. Will discuss at next site visit.
|
Application received | | | 7/12/2007 | | |
|
|
|
Initial letter of request received. Copy attached.
|