MIS-Aging Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 | | DONE |
Tom Arcoraci
|
|
|
|
DOC - Permit Finaled | 11/16/2010 | 11/16/2010 | 11/16/2010 | P | PASS |
Tom Arcoraci
|
|
|
|
FIR-Conference | 9/15/2010 | 9/16/2010 | 9/16/2010 | A | DONE |
Troy Cobbley
|
|
|
This is a partial inspection only. A full inspection can be completed when building plans have been issued. Additioal corrections may be required. 1 provide recertification of the kitchen hood fire suppression system or permit if modifications are required, 2 provide all required fire extinguishers with current inspection tags mounted in a normal path of travel, 3 repair/provide exit signs and emergency lighting, 4 provide single action hardware on the rear kitchen exit door and remove the dead bolt, 5 provide sticker "Door to remain unlocked while building is occupied" at the main exit with the keyed hardware, 6 provide building address on both street sides of the building with atleast 4" high numbers of a contrasting color, 7 provide current occupant load signage.
|
MEC-Conference | 9/15/2010 | 9/16/2010 | 9/16/2010 | A | FAIL |
Troy James
|
|
|
Dalina - ###-#### - call 30 mins prior to going need mechanical engineer approval to use existing kitchen equipment and hood system
|
Application received | | | 9/15/2010 | | |
|
|
|
|
Issue Misc Permit............ | | | 9/15/2010 | | |
|
|
|
|