MIS-Aging Inspection | 5/28/2015 | 5/28/2015 | 5/28/2015 | | DONE |
Bob Archibald
|
|
|
|
DOC - Permit Finaled | 5/28/2015 | 5/28/2015 | 5/28/2015 | P | PASS |
Bob Archibald
|
|
|
|
MIS-Aging Inspection | 1/27/2015 | 1/27/2015 | 1/27/2015 | | DONE |
Bob Archibald
|
|
|
|
ELE-Conference | 9/22/2014 | 9/22/2014 | 9/22/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Due to no activity securing permit from electrical contractor for service uupgrade to solve over heating issues. Section 4-05-28 ENFORCEMENT THROUGH DISCONNECTION OF POWER It shall be unlawful for any person, firm, association or corporation to install electrical wiring, equipment, apparatus or fixtures in violation of any rule or provision of this code or to use, cause or permit to be used any electrical installation that is hazardous to life or property within Boise City. A. If the Electrical Inspector shall find any part of any electrical wiring, equipment, apparatus or fixture in, on or about any building or premise in Boise City to have been installed or altered without an electrical permit or not in compliance with the rules of this Boise Municipal Code Page 12 of 17 SUPPLEMENT NO. 42 Code or if any electrical wiring, equipment, apparatus or fixture is found to be immediate hazardous to life and property, the Electrical Inspector shall have the right and authority to cause such installation to be disconnected and to place a written correction notice upon the disconnected installation. The Inspector shall, at the same time, give notice of such disconnection to the owner or occupant of the building or premise and/or to the person(s) using electric current carried by the disconnected installation that the disconnection has been made. Such notice shall be made by the most reasonably effective means and a written notice. Posted correction notice informing of action.
|
CHANGE STATUS TO (I) | | | 9/22/2014 | | DONE |
Tisha Gallop
|
|
|
still need to resolve electrical issues per insp 327
|
BLD-Conference | 7/18/2014 | 7/23/2014 | 7/28/2014 | A | DONE |
Jim Sly
|
|
|
LeeAndra ###-#### No life safety issues except Electrical. Deferred to Electrical and Mechanical. Mechanical contacted because new furnace and AC installed without permit, and need to verify that system is supplying only one space (unit).
|
DOC - Permit Finaled | 7/28/2014 | 7/28/2014 | 7/28/2014 | P | PASS |
Jim Sly
|
|
|
|
ELE-Conference | 7/18/2014 | 7/25/2014 | 7/25/2014 | A | DONE |
Rock A. Hudson
|
|
|
Reinspect unit for corrections compiance. Spoke with owner of bldg and explained the over heating issue. They are getting bids to correct electric issues. Tenant in unit A has moved out. Due to reduced demand at this time main breaker feeding 7155 is cool to touch as well as sub panel feeders. Will re check in 2 weeks.
|
ELE-Conference | 7/25/2014 | 8/8/2014 | 7/25/2014 | A | CANC |
Rock A. Hudson
|
|
|
Reinspect unit for corrections compiance
|
BLD-Conference | 7/16/2014 | 7/18/2014 | 7/18/2014 | A | CANC |
Jim Sly
|
|
|
(apt B) Substandard renters complaint concrete walls in bathroom crumbling, dry rot walls and ceiling, leaking around light fixture in ceiling, electrical problems with power going out alot, exposed wires in apartment, panel box is hot to touch, concerned with not enough power supply for 4 units in building.// Leeandra ###-####
No Imminent structural hazards. Electrical to investigate Electr problems. Rock Hudson.
|
MEC-Conference | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PART |
Alan Hauser
|
|
|
(apt B) per electrical inspector A/C unit installed without permit causing overload on electrical system.owner number is ###-#### ron and sharon kirkoman. talked to owner he was unaware that contractor had not pulled permit, will take care of it he said.
|
ELE-Conference | 7/16/2014 | 7/18/2014 | 7/18/2014 | A | FAIL |
Rock A. Hudson
|
|
|
(apt B) Substandard renters complaint concrete walls in bathroom crumbling, dry rot walls and ceiling, leaking around light fixture in ceiling, electrical problems with power going out alot, exposed wires in apartment, panel box is hot to touch, concerned with not enough power supply for 4 units in building.// Leeandra ###-#### BCC 4-05-18- lectrical permit required on AC unit added to Appt. A. NEC 230.72(C)- Each tenant shall have access to accupants service. NEC 230.79(C)- Each appt. single family dwelling and shall have minimum service rating of 100 amps for each unit. Bldg originally designed for duplex. Building owner shall seek conditional use approval for use as 4-plex. 7 days to secure electrical contractor for over load issue. 7 days to secure mechanical permit for HVAC equiptment added.
|
Issue Misc Permit............ | | | 7/16/2014 | | DONE |
|
|
|
|
Issue Misc Permit............ | | | 7/16/2014 | | DONE |
|
|
|
|
Application received | | | 7/16/2014 | | |
|
|
|
|