MIS-Aging Inspection | 1/19/2018 | 1/19/2018 | 1/19/2018 | | PASS |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 1/19/2018 | 1/19/2018 | 1/19/2018 | P | PASS |
Mike Jordan
|
|
|
Per inspector #445, work was completed and passed.
|
ELE-Final | 10/11/2017 | 10/11/2017 | 10/11/2017 | P | PASS |
Daryl DeGrange
|
|
|
job completed, final ok
|
MIS-Aging Inspection | 10/11/2017 | 10/11/2017 | 10/11/2017 | | PASS |
Daryl DeGrange
|
|
|
Manager hired electrical contractor to repair broken receptacles, job complete. final ok
|
MIS-Aging Inspection | 7/12/2017 | 7/12/2017 | 7/12/2017 | | DEFR |
Mike Jordan
|
|
|
This needs to go to electrical.
|
MIS-Aging Inspection | 4/3/2017 | 4/3/2017 | 4/4/2017 | | DEFR |
Mike Jordan
|
|
|
|
MIS-Aging Inspection | 11/15/2016 | 11/15/2016 | 11/16/2016 | | DEFR |
Mike Jordan
|
|
|
|
MIS-Aging Inspection | 6/10/2016 | 6/10/2016 | 6/10/2016 | | DEFR |
Mike Jordan
|
|
|
|
ELE-Final | 2/3/2016 | 2/4/2016 | 2/4/2016 | A | FAIL |
Daryl DeGrange
|
|
|
customer complaint-says all the wall fixtures under tables on west wall are uncovered-right where kids sit Broken receptacle under table in need of immediate repair. NEC 314.25 Covers and canopies, each box shall have a cover
|
Application received | | | 2/3/2016 | | |
|
|
|
|
Issue Misc Permit............ | | | 2/3/2016 | | DONE |
|
|
|
|