DOC - Permit Expired | 3/8/2018 | 3/8/2018 | 3/8/2018 | A | PASS |
Jim Storey
|
|
|
Expires: 03/06/18 open ele
|
MIS-Aging Inspection | 3/8/2018 | 3/8/2018 | 3/8/2018 | | PASS |
Jim Storey
|
|
|
Expires: 03/06/18
|
MIS-Aging Inspection | 12/7/2017 | 12/7/2017 | 12/12/2017 | | DEFR |
Jim Storey
|
|
|
ele c/n
|
PLM-Conference | 9/7/2017 | 9/7/2017 | 9/7/2017 | P | PASS |
Eric Strole
|
|
|
Kristi Phone #: ###-####-Plumbing is all maintenance issues.
|
ELE-Conference | 9/7/2017 | 9/7/2017 | 9/7/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Kristi Phone #: ###-#### 200.4- Grounded conductor of a multiwire branch circuit shall carry only the unbalanced load. Both ungrounded conductors on same phase. Possible overload of grounded conductor. 210.23- Appliances or electrical equipment fastened in place shall not exceed 50% of the rating of branch circuit. Window mounted AC units and bath fan/light/heater combo all require dedicated circuits. Circuit overload causing sparks and smell of smoke. 400.8- Flexible cords shall not run through walls or doorways. 16-3 runs from living room to bedroom for window mounted AC unit which is burned up. BCC 04-05-15- Licensed contractor required for repairs. Homeowners exemption does not apply to rental units.
|
BLD-Conference | 9/7/2017 | 9/7/2017 | 9/7/2017 | P | DONE |
Brandon Shaw
|
|
|
1) Roof is single layer, 3 tab: not installed per manufactures instalation instructions 2) Flashing at roof eaves and wall lines not adequate/needs replaced 3) Front porch/stairs settling, 1 1/2' variance left to right.
|
Application received | | | 9/7/2017 | | |
|
|
|
|
Issue Misc Permit............ | | | 9/7/2017 | | DONE |
|
|
|
|