MIS-Aging Inspection | 11/21/2019 | 11/21/2019 | 11/21/2019 | | PASS |
Jim Storey
|
|
|
|
DOC - Permit Finaled | 11/21/2019 | 11/21/2019 | 11/21/2019 | P | PASS |
Jim Storey
|
|
|
|
PLM-Conference | 12/27/2018 | 12/27/2018 | 12/27/2018 | A | PASS |
Eric Strole
|
|
|
A plumbing permit has been pulled for work.
|
PLM-Conference | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | FAIL |
Eric Strole
|
|
|
Leticia Phone #: ###-####-A plumbing permit is required .
|
MEC-Conference | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | PASS |
Jack Reynolds
|
|
|
Leticia Phone #: ###-#### - final ok - signed card for occ
|
PLM-Final | 12/14/2018 | 12/14/2018 | 12/17/2018 | P | PART |
Eric Strole
|
|
|
Leticia Phone #: ###-####-Need to install a RPBA on dishwasher. Need to install a DBCA on all ice machines before filter systems. Need to install a RPBA on coffee maker and sepereate from soda RPBA. Need to secure all backflows to wall. All backflows need tested.
|
MEC-Final | 12/14/2018 | 12/14/2018 | 12/14/2018 | P | FAIL |
Jack Reynolds
|
|
|
Leticia Phone #: ###-#### - need grease pans installed on all hoods - need to tether one peice of equipment and two others need wheels removed if no tethers are going to be installed - filter needs replaced in one hood due to damage
|
Issue Misc Permit............ | | | 12/13/2018 | | DONE |
|
|
|
|
Application received | | | 12/12/2018 | | |
|
|
|
|
Issue Misc Permit............ | | | 12/12/2018 | | DONE |
|
|
|
|