INSP-Final | 5/12/2015 | 5/13/2015 | 5/13/2015 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Hood suppression functioned correctly
|
INSP-Final | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | FAIL |
Troy Cobbley
|
|
|
Cable did not release automatically and the gas did not shut off as required. Power to the lights did shunt.
|
INSP-Sprinkler Rough-in/Hydro | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2845608 >> Inspection requested via mobile web by Jordan Taylor
|
INSP-Final | 5/11/2015 | 5/11/2015 | 5/11/2015 | P | CANC |
Troy Cobbley
|
|
|
Per contractor the hood suppression system/electrical shunt is not wired correctly. No inspection was performed.
|