Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberNAF16-00017
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY
Site Address 201 E 41ST ST
Project NameJIMMY'S AUTO BODY
Customer Number 
ePlanReviewNo
Description
Pre-engineered dry chemical system for spray paint booth.

Note: The dry chemical system does not remove the requirement for fire sprinklers in the spray paint booth, if the building is to be considered a fully sprinklered building. Fire sprinklers are still required. (Ref: NFPA 13: 4.1 and 22.4)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final3/24/20163/28/20163/28/2016PPASS
DetailsTroy Cobbley
Permit finaled
Sprinkler Plan Check3/24/2016 3/24/2016 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  3/24/2016 DONE
Permit Ready to Issue  3/24/2016 DONE
CHANGE STATUS TO (ISS)  3/24/2016 DONE
plan mod complete-sent back to North Ada County
Plan Modification Accepted  3/15/2016 DONE
plan mod excepted-received 2 sets of plan reviewfor spray booth-put in fire cubby for Tim F
INSP-Sprinkler Rough-in/Hydro3/7/20163/8/20163/8/2016ADONE
DetailsTroy Cobbley
Todays inspection request was a conference to discuss the classI electrical at the door to the paint booth. The contractor is to meet the 3' vertical and 5' horizontal requirement for the class I wiring. Also per Scott and my discussion the owner is to provide signage at both sides of the overhead doors (no smoking, no welding, no grinding..ect.) instead of meeting the 6' clearance requirement from exterior walls. The 6' requirement can't be met due to meeting the 30' from property line requirement. All references are derived from the 2012 IFC chapter 24.
INSP-Final3/2/20163/3/20163/3/2016AFAIL
DetailsKatie Marron
Inspection failed. The following items need to be corrected and reinspected:
-Plan modification required for installed piping changes.
-System Test
-Exhaust ventilation per IFC 2404.7.6 specifically meeting 6' from exterior wall
-Electrical wiring per IFC 2404.9.4 (explosion proof outlets and exit sign)

4A-40BC fire extinguisher installed during inspection.
1st review completed  2/29/2016 PASS
Sprinkler Plan Check2/29/2016 2/29/2016 PASS
DetailsTim Frost
Plan assigned to (Tim)2/29/2016 2/29/2016 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  2/29/2016 DONE
Permit Ready to Issue  2/29/2016 DONE
Issue and Courier  2/29/2016 DONE
Application received  2/23/2016  
Plan assigned to (Scott)2/23/2016    
DetailsScott Arellano
Plan assigned to (Tim)3/15/2016    
DetailsTim Frost