Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberNAF16-00040
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 6171 GLENWOOD ST Unit: 107
Project NameCOSMO PROF
Customer Number 
ePlanReviewNo
Description
Provide duct detection for a tenant improvement in an existing building. Actual address is 6711 N. Glenwood St.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final6/30/20166/30/20166/30/2016PPASS
DetailsKatie Marron
Duct smoke detectors tested satisfactory. Address is wrong on permit case, it is 6711 Glenwood, fire alarm is programed with correct address. Scope of work complete. Permit Finaled.
Telephone call  6/29/2016 DONE
Kenny called to say that an additional roof top unit is being provided that will require a 2nd duct smoke detector. He wanted to know if a resubmittal would be required. I told him that as built drawings showing all changes would be required to be submitte to NACFR prior to completion of the job and that they would be required at the fire alarm inspection for the inspector to review.
Alarm Plan Check6/17/2016 6/17/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2016 DONE
Resubmittal approved with review comments and notation on drawing. Taken to Candy for processing.
Permit Ready to Issue  6/17/2016 DONE
Issue and Courier  6/17/2016 DONE
put in inner office mail to go to NACFR
Plan resubmittals received  6/15/2016 DONE
resubmittals recreived permit app, 4 sheets of FA-1 & calcs-put in cubby for Lee M
Alarm Plan Check5/31/2016 5/31/2016 FAIL
DetailsLee G Meredith
1st review completed  5/31/2016 FAIL
See first review comments.
Telephone call  5/31/2016 DONE
called Sarah to let know permit failed and is heading back to NACFR-she will gice the massage to Josiah
Application received  5/23/2016  
Plan assigned to (Lee)5/23/2016    
DetailsLee G Meredith