Permit NumberNAF17-00002
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 9995 W STATE ST
Project NameGRACE ASSISTED LIVING ADDITION
Customer Number 
ePlanReviewNo
Description
Add detection, manual alarms, door release, horn strobe notification, duct detection and CO detection to an existing fire alarm system. Associated with NAF16-00045.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  8/22/2017 DONE
Mary called to see if we would allow as built documentation for a Health and Welfare requirement to add four low frequency horn strobes and an associated power supply. I told het that since it was a state requirement, we would allow as builts and that calculations would be required. If it wasn't a state requirement, we would have required a plan modification.
Permit Ready to Issue  7/6/2017 DONE
CHANGE STATUS TO (ISS)  7/6/2017 DONE
emailed Shelley that the plan mod was heading her way-Lee was fine with an extra fee for plan review
DOC - Permit Finaled  7/6/2017 DONE
as per Lee M and Scott A.-permit is complete
INSP-Final6/29/20176/30/20176/30/2017AFAIL
DetailsTroy Cobbley
Plan modifications are required for the changes in the candellas of the wall mounted strobes in the Residence Rooms. I verified the fire sprinkler interconnections with the existing fire alarm panel but stopped the inspection after finding multiple wall mount strobes overspaced in the Resident Rooms. I have not tested horns, strobes, smoke detectors, door release or hvac shutdown.
INSP-Final6/30/20176/30/20176/30/2017PPASS
DetailsScott Arellano
Re-inspection after plan modification. Pass.
Plan Modification Accepted  6/30/2017 DONE
received two sets of revised sheets marked FA-001, FA-002, FA-101, FA-102, FA-201, FA-501, FA-601, FA-602, FA-701, FA702 & FA-703; pland taken to LGM for review
Plan assigned to (Lee)6/30/2017 6/30/2017 DONE
DetailsLee G Meredith
Alarm Plan Check6/30/2017 6/30/2017 PASS
DetailsLee G Meredith
Alarm Plan Check6/29/2017 6/29/2017 PASS
DetailsLee G Meredith
Plan Modification Accepted  6/29/2017 DONE
plan mod recieved 4 sets of FA-001, FA-002, FA-101, FA-102, FA-201, FA-501, FA601,FA-602, FA-701, FA-702 & FA-703-GAVE TO lEE m
CHANGE STATUS TO (ISS)  6/29/2017 DONE
put in inner office mail to go back to NACFR-will go out 6-30-17 in the AM-i let Shelley know they were ready and coming back her way. They're closed Friday so will go out monday
1st review completed  1/10/2017 PASS
Alarm Plan Check1/10/2017 1/10/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/10/2017 DONE
Review approved with connemts.
Permit Ready to Issue  1/10/2017 DONE
Issue and Courier  1/10/2017 DONE
emailed Shelley that it was on it's way
Application received  1/9/2017  
Plan assigned to (Lee)1/9/2017 1/9/2017 DONE
DetailsCandy A. Nichols
put in cubby for Lee M