INSP-Final | 2/11/2017 | 2/15/2017 | 2/15/2017 | A | PASS |
Katie Marron
|
|
|
Scope of Work Complete. Permit Finaled.
|
Plan resubmittals received | | | 1/27/2017 | | DONE |
|
|
|
resubmittals received 6 sets of A-1 & A-2-4 large & 2 smaller sets-took to Lee M
|
Alarm Plan Check | 1/27/2017 | | 1/27/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/27/2017 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 1/27/2017 | | DONE |
|
|
|
|
Issue and Courier | | | 1/27/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 1/19/2017 | | 1/19/2017 | | FAIL |
Lee G Meredith
|
|
|
Not all items addressed from the previous review comments. Design still needs weatherproof notification in the locker/shower rooms and 1st floor corridor strobe is still inadequate. Emailed Kenny to let him know.
|
Miscellaneous action | | | 1/19/2017 | | DONE |
|
|
|
emailed Shelley and called Mike Sparrow (as well as emailed the plan review comments) that permit failed-put in inner office mail to Shelley
|
Plan resubmittals received | | | 1/18/2017 | | DONE |
|
|
|
resubmittals recieved 5 sets of sheet A-2 & A-1, 1 app 1 set of calcs-took to Lee M-emailed Shelley that the customer dropped them off
|
Application received | | | 1/17/2017 | | |
|
|
|
|
1st review completed | | | 1/17/2017 | | FAIL |
|
|
|
Notification inadequate in some areas. See review comments.
|
Miscellaneous action | | | 1/17/2017 | | DONE |
|
|
|
Emailed review comments to applicant.
|
Miscellaneous action | | | 1/17/2017 | | DONE |
|
|
|
sent Shelley an email-plan review finaled and plans are heading back her way
|
Plan assigned to (Lee) | 1/17/2017 | | | | |
Lee G Meredith
|
|
|
|