Permit Information
Permit NumberNAF17-00052
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 8250 MARIGOLD
Project NameEMERSON HOUSE ADDITION
Customer Number 
ePlanReviewNo
Description
Extend existing smoke detection and notification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final10/3/201710/4/201710/4/2017ADONE
DetailsTroy Cobbley
Permit finaled. A/v's have been syn'c and as-buiilts submitted
DOC - Permit Finaled  10/4/2017 DONE
Final Per Troy Cobbley
INSP-Alarm Testing10/2/201710/2/201710/2/2017PFAIL
DetailsTroy Cobbley
Audibles are not sync't, two strobes did not function, no as-builts, delay egress doors are not tied into fire alarm system yet.
Permit Ready to Issue  10/2/2017 DONE
CHANGE STATUS TO (ISS)  10/2/2017 DONE
emailed Shelley that the plan mod was coming her way
Plan Modification Accepted  9/29/2017 DONE
plan mod dropped off by Absolute Fire Protection-Shelley was out today so one of the others in the office at NACFR ok'd Absolute to bring it here-took to Lee-no app to attach to documents
CHANGE STATUS TO (REV)  9/29/2017 DONE
1st review completed  9/29/2017 PASS
Added low frequency sounders to sleeping units.
Alarm Plan Check9/29/2017 9/29/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/29/2017 DONE
Taken to Candy for processing. No additional review comments.
INSP-Final9/25/20179/26/20179/26/2017AFAIL
DetailsTroy Cobbley
There were no city approved plans or small documents on site for inspection. It appears that notification will need to be added in the corridor and in the common Shower Room. Also detection will need to be provided in the same Shower Room. Notification is shown in the corridor as existing but is not there. As-builts or Plan Mods will need to be provided to plan review. He will decide which will need to be provided.
Telephone call  9/26/2017 DONE
Mike from Absolute called regarding design changes noted by the inspector. I told him that due to the quantity of items plus the addidtion of a notification panel that a resubmittal will be required. Mike asked if heat detectors can be wall mounted. Informed him they could if located at least 4 inches from ceiling but no more than 12 inches per NFPA 72.
Telephone call  9/26/2017 DONE
Mary called to say that the added NAC panel was previously approved in a plan modification. If so, the contractor needs to have those approved plans on site for inspections. Also, if the approved plans show this, the addedf heat and notification in the shower room can be submitted in as built drawings.
INSP-Final9/22/20179/25/20179/25/2017ACANC
DetailsTroy Cobbley
After ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in8/17/20178/18/20178/18/2017ACANC
DetailsTroy Cobbley
Tenting Phone #: ###-#### Inspection requested via web by Sam Ball
Permit Ready to Issue  8/4/2017 DONE
Issue and Courier  8/4/2017 DONE
put in inner office mail and email Shelley
Plan assigned to (Lee)8/1/2017 8/3/2017 DONE
DetailsLee G Meredith
1st review completed  8/3/2017 PASS
Alarm Plan Check8/3/2017 8/3/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/3/2017 DONE
Plans approved with review comments.
Miscellaneous action  8/1/2017 DONE
emailed Shelley what the permit # is
Application received  8/1/2017