INSP-Final | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | DONE |
Jim Page
|
|
|
Final commercial hood fire suppression system inspection complete.
|
DOC - Permit Finaled | | | 12/12/2017 | | DONE |
|
|
|
Doc final Per Jim Page
|
INSP-Final | 12/7/2017 | 12/8/2017 | 12/8/2017 | A | FAIL |
Jim Page
|
|
|
Gas valve did not automatically shut down with west side hood fire suppression system activation, valve did shut gas off on east side hood suppression system activation. System will need to be retested for energy source isolation during hood activation.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/28/2017 | | DONE |
Scott Arellano
|
|
|
Plans taken to permit technician.
|
Sprinkler Plan Check | 9/28/2017 | | 9/28/2017 | | PASS |
Scott Arellano
|
|
|
No seperate comments attached for this pre-engineered hood suppression system. Final inspection and functional puff test is required; as per conditions of approval in application.
|
Permit Ready to Issue | | | 9/28/2017 | | DONE |
|
|
|
|
Issue and Courier | | | 9/28/2017 | | DONE |
|
|
|
emailed Shelley that the permit is in the inner office mail coming her way
|
Application received | | | 9/26/2017 | | |
|
|
|
|