Permit Information
Permit NumberNAF17-00088
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 2900 CHINDEN BLVD
Project NameRIVERSIDE KITCHEN MAU 1&2
Customer Number 
ePlanReviewNo
Description
Provide duct smoke detection and shutdown on a 10,500 cfm mixed air unit and shutdown on a 6,500 cfm mixed air unit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final1/11/20181/12/20181/12/2018PPASS
DetailsScott Arellano
Follow up inspection passed.
DOC - Permit Finaled  1/12/2018 DONE
Per Scott A
INSP-Final1/10/20181/11/20181/11/2018PFAIL
DetailsTroy Cobbley
Need a plug for the end of the sample tube and the duct smoke detector repaired. Per Troy James and Lee it appears the duct smoke detector is not even required in a make up air unit so there is the option of removing the equipment and voiding the permit.

Tech-John Howard Phone #: ###-#### Inspection requested via web by John Siewert
1st review completed  12/19/2017 PASS
Sprinkler Plan Check12/19/2017 12/19/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/19/2017 DONE
Plans approved with review comments.
Permit Ready to Issue  12/19/2017 DONE
Issue and Courier  12/19/2017 DONE
Application received  12/15/2017  
Plan assigned to (Lee)12/15/2017    
DetailsLee G Meredith