Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberNAF18-00013
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 511 E 43RD ST
Project NameGARDEN CITY SCHOOL
Customer Number 
ePlanReviewNo
Description
Provide a new addressable fire alarm system with sprinkler monitoring, elevator recall and shunt and emergency voice evacuation in a new building. This work is related to building permit NAF17-00064.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final8/8/20188/9/20188/9/2018ADONE
DetailsJim Page
Final fire alarm inspection complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
DOC - Permit Finaled  8/9/2018 DONE
close out permit per Jim Page
INSP-Final8/8/20188/8/20188/8/2018PFAIL
DetailsTroy Cobbley
Permit will be ok to final when the first and second floor elevator lobby doors close/latch upon release during fire alarm activation

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final8/5/20188/6/20188/6/2018AFAIL
DetailsTroy Cobbley
The elevator did not recall when the machine room detectyor was activated. The first and second floor levator lobby doors do not close/latch. Still need to test the shunt in the machine room.


Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final8/2/20188/3/20188/3/2018AFAIL
DetailsTroy Cobbley
I left message for contact that I was on the way to the project. Arrived at the project and called again but could only leave another voice mail. No inspection performed.


Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final8/2/20188/2/20188/2/2018AFAIL
DetailsTroy Cobbley
Need as-builts, need to test elevator, need elevator doors on first and second floors to latch, need strobe raised in third floor restroom, need speaker added in third floor mech room, need correct size batteries in facp.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final7/31/20188/1/20188/1/2018PFAIL
DetailsTroy Cobbley
For todays inspection I verified the facp panel, voice evac panel, phone lines, and spacing of the notification devices. We also tested all of the fire sprinkler devices. I noted a notification device that is needed in the third floor storage room, and acouple devices that are overspaced and a wall mount device in the third floor restroom that is mounted too low. We have not tested any notification devices or duct smoke detectors. As-builts need to be submitted showing the additional devices/addressing.


Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final7/30/20187/31/20187/30/2018PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, July 30, 2018.
1st review completed  2/28/2018 PASS
Alarm Plan Check2/28/2018 2/28/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/28/2018 DONE
Plans approved with review comments and drawing notation / requirements.
Permit Ready to Issue  2/28/2018 DONE
Issue and Courier  2/28/2018 DONE
emailed Shelley and put in inner office mail to go out tomorrow
Application received  2/26/2018  
Plan assigned to (Lee)2/26/2018   L
DetailsLee G Meredith