INSP-Final | 6/1/2018 | 6/4/2018 | 6/4/2018 | A | DONE |
Troy Cobbley
|
|
|
Life safety passed. Correction made.
Call prior to going Phone #: 2087132042 >> Inspection requested via mobile web by Ryan
|
DOC - Permit Finaled | | | 6/4/2018 | | DONE |
|
|
|
Per Troy C
|
INSP-Final | 5/22/2018 | 5/22/2018 | 5/22/2018 | P | FAIL |
Troy Cobbley
|
|
|
Remove the thumbturn deadolt from the main exit and provide keyed with indicator, Provide exit signs as shown with door hardware that provides free travel as discussed in the office area, Remove he thumbturn deadbolt from the norhtwest exit door and provide single action hardware, Provide sprinkler protection under the tanks or provide exception, provide Occupant Load sign, provide Riser Room sticker.
Call prior to going Phone #: 2087132042 >> Inspection requested via mobile web by Ryan Allen
|
Staff review | 4/10/2018 | 4/10/2018 | 4/10/2018 | | PASS |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 4/10/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 4/10/2018 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 3/26/2018 | | 3/28/2018 | | FAIL |
Tim Frost
|
|
|
as per Tim F-failed review and sent to Shelley
|
Miscellaneous action | | | 3/26/2018 | | DONE |
|
|
|
emailed Shelley and Tim F what the permit # is
|
Application received | | | 3/26/2018 | | |
|
|
|
|