Permit Information
Permit NumberNAF18-00055
StatusFinaled
Name BRANDON BOOMGARDEN
Site Address 514 E 46TH ST
Project NameOCCFY2018-0020
Customer Number 
ePlanReviewNo
Description
OCCFY2018-0020 BB Enterprises Inc occupancy review only, occupant load set by DBS
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final8/10/20188/10/20188/10/2018PDONE
DetailsJim Page
Previously noted items have been completed, Ron Johnson with Boise Fire approved the 18 foot wide gate opening to remain, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.

Phone #: 2088301685 >> Inspection requested via mobile web by Brandon
DOC - Permit Finaled  8/10/2018 DONE
doc-final per Jim Page
INSP-Final8/2/20188/7/20188/7/2018AFAIL
DetailsTroy Cobbley
Provide fire extinguishers as discussed and a 20' clear width for the gate.

Call prior to going Phone #: 2088301685 >> Inspection requested via mobile web by Brandon
Staff review5/16/20185/16/20185/22/2018 PASS
DetailsAdele J Schaffeld-Griffin
resubmitted 5-16-18
PLANS/APPL TAKEN TO FRONT DESK  5/22/2018 DONE
Permit Ready to Issue  5/22/2018 DONE
Issue and Courier  5/22/2018 DONE
emailed Shelley
Staff review4/25/20184/25/20184/25/2018 FAIL
DetailsAdele J Schaffeld-Griffin
see original change mark. The tenant space requires 2 exits based on occupant load established by DBS. When 2 exits are required they only count as 2 exits if they are separated by 1/2 the diagonal distance in a non sprinklered building. You also have to swing the door in the direction of egress travel when you are required to have 2 exits. You are also required to have illuminated exit signs and emergency egress lighting along with the correct door hardware. The floor plan had not been changed to address the original egress items other than a note 2nd man door. Please provide 2 code compliant egress doors.
Staff review4/20/20184/20/20184/20/2018 FAIL
DetailsAdele J Schaffeld-Griffin
Occupant load of 50 as established by DBS requires 2 exits, exit signage emergency egress lighting, door swing in direction of travel, door hardware and exit separation IFC chapter 10
Application received  4/13/2018  
Plan assigned to (Adele)4/13/2018    
DetailsAdele J Schaffeld-Griffin