INSP-Final | 8/10/2018 | 8/10/2018 | 8/10/2018 | P | DONE |
Jim Page
|
|
|
Previously noted items have been completed, Ron Johnson with Boise Fire approved the 18 foot wide gate opening to remain, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Phone #: 2088301685 >> Inspection requested via mobile web by Brandon
|
DOC - Permit Finaled | | | 8/10/2018 | | DONE |
|
|
|
doc-final per Jim Page
|
INSP-Final | 8/2/2018 | 8/7/2018 | 8/7/2018 | A | FAIL |
Troy Cobbley
|
|
|
Provide fire extinguishers as discussed and a 20' clear width for the gate.
Call prior to going Phone #: 2088301685 >> Inspection requested via mobile web by Brandon
|
Staff review | 5/16/2018 | 5/16/2018 | 5/22/2018 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
resubmitted 5-16-18
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/22/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 5/22/2018 | | DONE |
|
|
|
emailed Shelley
|
Staff review | 4/25/2018 | 4/25/2018 | 4/25/2018 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
see original change mark. The tenant space requires 2 exits based on occupant load established by DBS. When 2 exits are required they only count as 2 exits if they are separated by 1/2 the diagonal distance in a non sprinklered building. You also have to swing the door in the direction of egress travel when you are required to have 2 exits. You are also required to have illuminated exit signs and emergency egress lighting along with the correct door hardware. The floor plan had not been changed to address the original egress items other than a note 2nd man door. Please provide 2 code compliant egress doors.
|
Staff review | 4/20/2018 | 4/20/2018 | 4/20/2018 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
Occupant load of 50 as established by DBS requires 2 exits, exit signage emergency egress lighting, door swing in direction of travel, door hardware and exit separation IFC chapter 10
|
Application received | | | 4/13/2018 | | |
|
|
|
|
Plan assigned to (Adele) | 4/13/2018 | | | | |
Adele J Schaffeld-Griffin
|
|
|
|