INSP-Final | 8/10/2018 | 8/10/2018 | 8/10/2018 | A | DONE |
Jim Page
|
|
|
Final fire alarm inspection complete.
|
DOC - Permit Finaled | | | 8/10/2018 | | DONE |
|
|
|
doc-final per Jim Page
|
INSP-Final | 8/8/2018 | 8/9/2018 | 8/9/2018 | A | PART |
Jim Page
|
|
|
Final fire alarm inspection complete for activation and visual inspection, as noted in last inspection as builts will be required to be submitted before final can be completed.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final | 8/1/2018 | 8/2/2018 | 8/2/2018 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for corrections needed which include strobe coverage issues in the Gym due to STI covers on the strobes, overspaced strobes and areas where strobes are needed. As-builts will be required prior to a final sign off.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Permit Ready to Issue | | | 5/14/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 5/14/2018 | | DONE |
|
|
|
emailed Shelley that it was in the inner office mail heading her way
|
Staff review | 4/11/2018 | 4/11/2018 | 5/11/2018 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 5/11/2018 | | 5/11/2018 | | PASS |
Lee G Meredith
|
|
|
Resubmittal approved as noted.
|
PLANS TAKEN FRONT DESK ALARM | | | 5/11/2018 | | DONE |
|
|
|
Plans approved as noted with review comments and requirements.
|
Plan resubmittals received | | | 5/10/2018 | | DONE |
|
|
|
resubmittals were turned in by customer since NACFR was closed per Shelley-4 each FA0.0, FA0.1, FA1.0, FA2.0 & FIRE ALARM PACKET- took to Lee M
|
Plan assigned to (Lee) | 5/2/2018 | | 5/2/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/2/2018 | | FAIL |
|
|
|
Existing horn strobes are being replaced with speaker strobes. Candela for existing locations has not been provided. Discussed this with Adam Bayne via telephone. He agreed. Design is to be corrected and resubmitted.
|
Miscellaneous action | | | 4/25/2018 | | DONE |
|
|
|
emailed Shelley the app and the permit #
|
Application received | | | 4/25/2018 | | |
|
|
|
|