INSP-Final | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | DONE |
Troy Cobbley
|
|
|
Life safety passed
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
|
DOC - Permit Finaled | | | 8/30/2018 | | DONE |
|
|
|
per Troy Cobbley doc final-inspection passed
|
INSP-Final | 8/22/2018 | 8/22/2018 | 8/22/2018 | P | FAIL |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
1- fire ext need corrected. height/tag/location
2-cylindars need to be restrained
3-clearance for all electrical equipment shall be provided
4- address signage required for all buildings
|
Staff review | 7/10/2018 | 7/10/2018 | 7/16/2018 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/16/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/16/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 7/16/2018 | | DONE |
|
|
|
emailed Shelley
|
Plan resubmittals received | | | 7/10/2018 | | DONE |
|
|
|
resubmittal in Garden city e plan
|
Plan assigned to (Adele) | 5/2/2018 | | 5/8/2018 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
No Fire Review completed at this time. Will review when corrected drawings are received as noted by building plan review. Please Clarify, fire sprinkler system note on drawings says "will be required" when will this be installed?
|
Miscellaneous action | | | 5/2/2018 | | DONE |
|
|
|
emailed Adele and Shelley
|
Application received | | | 5/2/2018 | | |
|
|
|
|