Information based on query as of Thursday, June 27, 2024.
Permit Information
Permit NumberNAF18-00068
StatusFinaled
Name CONVERGINT TECHNOLOGIES
Site Address 9779 W STATE ST
Project NameGRACE ASSISTED LIVING
Customer Number 
ePlanReviewNo
Description
Provide a fire alarm system in a state licensed assisted living facility.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final9/25/20189/27/20189/27/2018ADONE
DetailsTroy Cobbley
Permit finaled

Call prior to going Phone #: 2089196887 >> Inspection requested via mobile web by Derek
DOC - Permit Finaled  9/27/2018 DONE
DetailsTroy Cobbley
per Troy Cobbley-fire final passed
INSP-Final9/24/20189/25/20189/25/2018AFAIL
DetailsTroy Cobbley
Change the smoke detector to a heat and provide the CO detectors as per Lee's comments. Provide as-builts and document box. Provide testing of the type 1 hood suppression system and testing of the door mag interconnection.


Phone #: 2089196887 >> Inspection requested via mobile web by Derek
INSP-Final9/18/20189/21/20189/21/2018PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089196887 >> Inspection requested via mobile web by Dereck

Contractors not ready for inspections.
Meeting  9/21/2018 DONE
Emailed Derek to let him know the PIV monitoring was required.
Telephone call  8/24/2018 DONE
Derek call about how to program egress pull stations for private mode. I told him that he should contact Nate from the state offices as the system needs to meet state requirements for licensing purposes. I told Derek that we would follow their requirements, as long as they meet minimum NFPA 72 and IFC.
Miscellaneous action  6/27/2018 DONE
emailed Shelley that was on it's way threw inner office mail-well it will go out 6-18-18 because mail has already been picked up today
Telephone call  6/21/2018 DONE
Derek Ellis of convergint called to indicate that he felt he had the wrong drawings. Resubmittal was to have had an additional remote annunciator and pull station were not shown on the approved drawings. Added equipment was to allow for private mode operation. Mary Froemke is to resubmit drawings that show this additional equipment. I emailed Shelly to inform her that revised drawings will be delivered by Derek but since I approved the wrong set, there should not be any additional charge.
Staff review5/9/20185/9/20185/17/2018 PASS
DetailsLee G Meredith
Alarm Plan Check5/17/2018 5/17/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/17/2018 DONE
Plans approved with review comments and requirements.
Permit Ready to Issue  5/17/2018 DONE
Issue and Courier  5/17/2018 DONE
put in inner office mail to go to NACFR and emailed Shelley
Plan resubmittals received  5/15/2018 DONE
resubmittals received 4 sets of application, calcs, sheets FA.00, FA2.0 & FA2.1- took to Lee M
1st review completed  5/11/2018 FAIL
See 1st review comments for required corrections.
Telephone call  5/10/2018 DONE
Informed Mary Froemke that visible notification will be required in the dwelling unit baths, as they are considered common areas for visitors. She is to discuss this with the state inspector - Nate Elkins and Bret Anderson of Convergint.
Application received  5/9/2018  
Plan assigned to (Lee)5/9/2018    
DetailsLee G Meredith