Permit Information
Permit NumberNAF18-00084
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 3554 N PROSPECT LN
Project Name 
Customer Number 
ePlanReviewNo
Description
See NAF18-00086--per Shelley address change-old address was
3552 N Prospect Ln 7-3-19
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final7/18/20197/18/20197/18/2019PDONE
DetailsTroy Cobbley
Permit finaled.

Correction from RTC Insp to Fire Final Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in7/17/20197/18/20197/18/2019PCANC
DetailsTroy Cobbley
Wrong inspection type scheduled.

Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
DOC - Permit Finaled  7/18/2019 DONE
per troy cobbley
INSP-Final7/2/20197/3/20197/3/2019PFAIL
DetailsTroy Cobbley
Need the backflow preventor certified and the 2" valve removed as per discussion/plans. Address has been corrected.


Contact Andrew Larson ###-#### 30 min prior to final insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Final7/2/20197/3/20197/2/2019ACANC
DetailsTroy Cobbley
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in4/5/20194/8/20194/8/2019PCANC
DetailsJim Page
Inspection request was for NAF18-00086 unit, this request is cancelled.

Contact Andrew Larson ###-####-5068 30 min prior to RTC Insp Start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in3/8/20193/11/20193/11/2019PPASS
DetailsTroy Cobbley
The additional pendant has been added in the third floor mechanical room. Piping can be covered. Head to be shown on as-builts prior to a final sign off.

Contact Andrew Larson ###-#### 30 Min Prior to RTC Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in3/8/20193/14/20193/8/2019ACANC
DetailsTroy Cobbley
Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019APART
DetailsTroy Cobbley
The tenting inspection passed and piping can be covered. However I noticed a third floor closet appears to be used for mechanical. I spoke to Scott in Phoenix Fire office about this potential problem. Sprinkler protection may be required. He is going to follow up.

Andrew Larson Point of contact Phone #: ###-#### Inspection requested via web by Teri Cruickshank
Staff review9/19/20189/19/20189/25/2018 DONE
DetailsTim Frost
Permit Ready to Issue  9/25/2018 DONE
Issue and Courier  9/25/2018 DONE
emailed Shelley
Plan resubmittals received  9/19/2018 DONE
Resubmittals recieved all app's, letter from Phoenex Fire, owners info cert, calcs, steel hanger info, sheets 1 of 3, 2 of 3, 3 of 3-took to Tim F
Staff review6/21/20186/21/20189/11/2018 FAIL
DetailsTim Frost
Plan resubmittals received  8/28/2018 DONE
Resubmittals received 4 pkgs of each letter, hydraulic design pkgs, calcs & sheets FP1, 2 & 3-this set of plans is for 3544, 3552, 3560 & 3568 N Prospect Ln-per #'s NAF18-00086, 84, 83& 85-took to Adele
Application received  6/21/2018  
Miscellaneous action  6/21/2018 DONE
emailed Shelley
Plan assigned to (Tim)6/21/2018    
DetailsTim Frost