Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberNAF18-00085
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 3550 N PROSPECT LN
Project Name 
Customer Number 
ePlanReviewNo
Description
See NAF18-00086-per Shelley address change-old address was 3568 N Prospect Ln 7-3-19
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final7/18/20197/18/20197/18/2019PDONE
DetailsTroy Cobbley
Permit finaled

Correction from RTC Insp to Fire Final Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in7/17/20197/18/20197/18/2019PPASS
DetailsTroy Cobbley
Permit finaled
DOC - Permit Finaled  7/18/2019 DONE
per troy cobbley
INSP-Final7/2/20197/3/20197/3/2019PFAIL
DetailsTroy Cobbley
Need the backflow preventor certified and the 2" valve removed as per discussion/plans. Address has been corrected.

Contact Andrew Larson ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Final7/2/20197/3/20197/2/2019ACANC
DetailsTroy Cobbley
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro6/26/20196/27/20196/27/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in4/5/20194/8/20194/8/2019PCANC
DetailsJim Page
Inspection request was for NAF18-00086 unit, this request is cancelled.

Contact Andrew Larson ###-#### 30 min prior to RTC insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in3/8/20193/11/20193/11/2019PPASS
DetailsTroy Cobbley
The additional pendant has been added in the third floor mechanical room. Piping can be covered. Head to be shown on as-builts prior to a final sign off.


Contact Andrew larson ###-#### 30 Min prior to RTC Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in3/8/20193/14/20193/8/2019ACANC
DetailsTroy Cobbley
Contact Andrew Larson ###-#### 30 Min prior to RTC Insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019APART
DetailsTroy Cobbley
The tenting inspection passed and piping can be covered. However I noticed a third floor closet appears to be used for mechanical. I spoke to Scott in Phoenix Fire office about this potential problem. Sprinkler protection may be required. He is going to follow up.

Andrew Larson Point of contact Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in2/5/20192/6/20192/6/2019APASS
DetailsTroy Cobbley
The rough-in passed for the residence as marked/dated on the city approved plans. Piping can be covered on the first and second floors. Insulation to be installed above the piping on the third floor needs to be verified prior to a cover inspection for the third floor. this will be for Bldg A Lot 4

Tahnk YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
Permit Ready to Issue  9/25/2018 DONE
Issue and Courier  9/25/2018 DONE
emailed Shelley
Plan resubmittals received  9/19/2018 DONE
Resubmittals recieved all app's, letter from Phoenex Fire, owners info cert, calcs, steel hanger info, sheets 1 of 3, 2 of 3, 3 of 3-took to Tim F
Staff review6/21/20186/21/20189/11/2018 FAIL
DetailsTim Frost
Plan resubmittals received  8/28/2018 DONE
Resubmittals received 1 letter, 4 hydraulic design pkgs, calcs & 1
each of sheets FP1, 2 & 3-this set of plans is for 3544, 3552, 3560 & 3568 N Prospect Ln-per #'s NAF18-00086, 84, 83& 85-took to Adele
Plan resubmittals received  8/28/2018 DONE
Resubmittals received 4 pkgs of each letter, hydraulic design pkgs, calcs & sheets FP1, 2 & 3-this set of plans is for 3544, 3552, 3560 & 3568 N Prospect Ln-per #'s NAF18-00086, 84, 83& 85-took to Adele
Application received  6/21/2018  
Miscellaneous action  6/21/2018 DONE
emailed Shelley
Plan assigned to (Tim)6/21/2018    
DetailsTim Frost