Plan Modification Accepted | | | 8/10/2018 | | DONE |
|
|
|
as built plans brought in for Lee M
|
INSP-Final | 8/8/2018 | 8/9/2018 | 8/9/2018 | A | DONE |
Lee G Meredith
|
|
|
Permit ready for final
|
DOC - Permit Finaled | | | 8/9/2018 | | DONE |
|
|
|
as per Lee M-fire final passed so doc final
|
Miscellaneous action | | | 8/9/2018 | | DONE |
|
|
|
Received electronic copies of as built drawings, calcs. and monitoring station reports. All approved.
|
Miscellaneous action | | | 8/9/2018 | | DONE |
|
|
|
Final inspection - 2nd phone line repaired, strobe added, as built drawings corrected, notification troubles changed from supervisory to trouble, record of completion received.
|
INSP-Final | 8/6/2018 | 8/7/2018 | 8/7/2018 | A | FAIL |
Troy Cobbley
|
|
|
Phone line #2 needs repaired/tested, need as-builts and a strobe added in Building B.
Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny
|
Telephone call | | | 7/9/2018 | | DONE |
|
|
|
Kenny called to say they will not be providing strobes in storage areas. Only speakers. As built drawings and calcs are to reflect this minor change.
|
Staff review | 6/25/2018 | 6/25/2018 | 7/2/2018 | | PASS |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/2/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 7/2/2018 | | 7/2/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/2/2018 | | DONE |
|
|
|
Plans approved with review comments. Taken to Candy for processing.
|
Permit Ready to Issue | | | 7/2/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 7/2/2018 | | DONE |
|
|
|
meailed Shelley that it was in the inner office mail
|
Telephone call | | | 7/2/2018 | | DONE |
|
|
|
Calculation sheets show an extreeme deficiency for circuit FAS2-1. I discussed this with Kenny and he determined that an error was made on one entry. He emailed a corrected calc and it was within tolerance.
|
Miscellaneous action | | | 6/29/2018 | | DONE |
|
|
|
Kenny delivered corrected drawings. to Boise City Hall.
|
Telephone call | | | 6/27/2018 | | DONE |
|
|
|
Kenny Leslie called to say they have a major design change and that he will deliver changed drawings and calc within the next few days.
|
Application received | | | 6/26/2018 | | |
|
|
|
|
Miscellaneous action | | | 6/26/2018 | | DONE |
|
|
|
emailed Shelley the permit #
|