DOC - Permit Finaled | | | 10/2/2018 | | DONE |
|
|
|
final per Forrest
|
INSP-Final | 9/19/2018 | 9/19/2018 | 9/20/2018 | P | FAIL |
Adele J Schaffeld-Griffin
|
|
|
Forrest inspection comments-Site inspection completed. Building master keys installed at Knox Box. Permit final pending item #6 from previous correction notice dated 8/22/18. Per building owner John Wood, the paint booth will not be utilized and acknowledges the booth fire suppression system is not active. John agreed to a two week timeline to finish corrections and request a re-inspection. Call prior to going Phone #: 2084125969 >> Inspection requested via mobile web by John Wood
|
INSP-Final | 9/17/2018 | 9/17/2018 | 9/20/2018 | P | CANC |
Adele J Schaffeld-Griffin
|
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
|
INSP-Final | 9/4/2018 | 9/5/2018 | 9/5/2018 | P | FAIL |
Troy Cobbley
|
|
|
No plans or small documents. No inspection was performed. I went over general requirements. Jim Page noted that the suppression system appears to be in-operative for the paint booth.
Call prior to going Phone #: 2084125969 >> Inspection requested via mobile web by John
|
INSP-Final | 8/22/2018 | 8/22/2018 | 8/22/2018 | P | FAIL |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
-Not an inclusive or punch list
-Paint booth not included not part of this project will be permited at later date
1-remove all obstruciton from fire extinguishers
2-provide current tag on all fire extinguishers
3-provide address on all buildings
4-no storage over 12 fee in height
5-remove all hasp locks from exit doors
6-provide fire sprinkler protection in covered storage areas in rear of building
7-provide clear access to fire riser
8-provide clearance in front of electrical panels
9-provide clear path of egress from rear exit doors
10-provide small documents
discussed plaxtic curtain that is used on occasion for sanding and how it could impact fire sprinkler protection and interior finish materials
will need reinspect
|
Permit Ready to Issue | | | 8/22/2018 | | DONE |
|
|
|
|
Issue and Courier | | | 8/22/2018 | | DONE |
|
|
|
talked to Shelley over phone
|
Staff review | 7/30/2018 | 7/30/2018 | 8/9/2018 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/9/2018 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/30/2018 | | DONE |
|
|
|
|
Application received | | | 7/6/2018 | | |
|
|
|
|
Miscellaneous action | | | 7/6/2018 | | DONE |
|
|
|
emailed Shelley
|