Permit Information
Permit NumberNAF18-00128
StatusIssued
Name NACFR
Site Address 14156 N BALL MANOR LN
Project NameNAC- BALL MANOR RESIDENCE
Customer Number 
ePlanReviewNo
Description
[Ball Manor Residence]
***PLAN MOD APPROVED 1-14-2019 MAS***The fire sprinkler scope of work consists of a new single family two level home. The system is designed as a combination system supplied from a well. The system utilizes CPVC piping and residential type sprinklers.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final8/16/20198/20/20198/20/2019APASS
DetailsTroy Cobbley
*** Flow switch timed at 40 seconds*** Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
INSP-Final7/24/20197/30/20197/30/2019APASS
DetailsTroy Cobbley
**Hydro passed at well pump pressure. Bell needs to be mounted in relocated location I marked on approved plans, Not at the location submitted. Some patching needs to be done around escutcheons, and all painting needs to be completed before final inspection. MAS***
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
INSP-Final7/15/20197/17/20197/17/2019PCANC
DetailsTroy Cobbley
Cancel per contractor. Water connection not done yet.

Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian Rumple
INSP-Sprinkler Rough-in2/4/20192/4/20192/4/2019PPASS
DetailsTroy Cobbley
The remaining sprinkler piping is ok for cover.

Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John Venche
INSP-Sprinkler Rough-in1/28/20191/28/20191/28/2019PPART
DetailsTroy Cobbley
Rough-in passed. All piping, except as marked on the approved plans, can be covered. Tenting passed. Builder is going to add insulation in the garage area.

Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John
INSP-Sprinkler Rough-in1/22/20191/22/20191/22/2019PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John Inspection cancelled via mobile web on Tuesday, January 22, 2019.
Staff review1/15/20191/15/20191/15/2019 PASS
DetailsMark Stumbaugh
No fee for as built drawings
Plan assigned to (Stumbaugh)1/10/2019 1/14/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  1/14/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  1/14/2019 DONE
CHANGE STATUS TO (ISS)  1/14/2019 DONE
as per Mark Strumbaugh-no charge for the plan mod-emailed Shelley permit was ready
Plan Modification Accepted  1/10/2019 DONE
As built
INSP-Sprinkler Rough-in12/18/201812/20/201812/20/2018PFAIL
DetailsTroy Cobbley
Was only able to do a partial inspection due to numerous pipe routing changes. I also noted that alot of additional fittings have been added that might affect the hydraulic calculations. I also noted tenting issues in the garage area. Contractor will need to contact plan review and see if as-builts or plan modifications are required. This will need to be done prior to another inspection being scheduled. Per the general contractor blow-in insulation will be used above the ceilings in the garage.

Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
Staff review12/3/201812/3/201812/3/2018 PASS
DetailsTim Frost
Plan assigned to (Tim)12/3/2018 12/3/2018 DONE
DetailsTim Frost
Plan resubmittals received  12/3/2018 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  12/3/2018 DONE
DetailsTim Frost
Permit Ready to Issue  12/3/2018 DONE
Issue and Courier  12/3/2018 DONE
emailed Shelley permit was issued
Miscellaneous action  11/29/2018 DONE
DetailsTim Frost
Sent the following email based on Well supplier letter.

IHowever, you are still good 26 Gpm @ 54 Psi. The pump supplier is saying there is 54 Gpm @ 60 Psi.

The pump curve I found indicates 350’ (151 Psi) of Head at 26 Gpm. Pump set depth is 127’. So elevation loss would be 55 Psi.

The well could have as much as 96 Psi available but he says it is set at 130 Psi. Even with that, there should be 75 Psi available. He also indicates he flowed 54 Gpm for over an hour.

So I do not see a problem

Thank you for your time and help in this matter.
Plan resubmittals received  11/29/2018 DONE
Resubmittals recieved 4 sets of AFSS reports, FP1 both sheets 1 of 2 and 2of 2- took to Tim F
Staff review11/2/201811/2/201811/8/2018 FAIL
DetailsTim Frost
Plan resubmittals received  11/2/2018 DONE
Four copies of each fire protection packages and plans, stamped and taken to Tim F
Staff review10/17/201810/17/201810/24/2018 FAIL
DetailsTim Frost
Miscellaneous action  10/24/2018 DONE
emailed Shelley that the plan review failed
Miscellaneous action  10/17/2018 DONE
Emailed Shelley permit number.
Application received  10/17/2018  
Plan assigned to (Tim)10/17/2018    
DetailsTim Frost