Permit Information
Permit NumberNAF19-00019
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 5655 N GLENWOOD ST Unit: 101/102
Project NameGC
Customer Number 
ePlanReviewNo
Description
(Ashland Creek) This a new sprinkler system in a new single level building. The areas below the ceiling are protected by a tented wet system. The attic is protected by a dry pipe system. The upright sprinklers on the dry system are 4.2k with pipe that is corrosion resistant per 8.3.4.4.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final10/8/201910/8/201910/8/2019PDONE
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Sam Ball
DOC - Permit Finaled  10/8/2019 DONE
Per Troy C, 10/8/19 Final inspection
INSP-Final9/18/20199/19/20199/19/2019AFAIL
DetailsTroy Cobbley
Can final when heat is provided and the plastic is attached to the trusses (repaired) and insulation is provided at these patched areas. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final8/21/20198/22/20198/22/2019PPART
DetailsTroy Cobbley
Sprinkler work is complete. Temporary per Boise Fire. Permit can be finaled when the shell/core permit is finaled.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Final8/20/20198/21/20198/21/2019AFAIL
DetailsTroy Cobbley
There were problems with the fire alarm system which prevented testing of the sprinkler system. No testing performed.
Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro8/6/20198/7/20198/7/2019APASS
DetailsTroy Cobbley
24 hour air test on dry system and hydrostatic test on wet system witnessed with no pressure loss. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Conference8/5/20198/6/20198/6/2019PDONE
DetailsTroy Cobbley
Myself, sam and the job superintendant spoke about a temporary occupancy for the two tenants until a third middle tenant is found with-in the next couple months. I deferred the request to the fire dept.

Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
INSP-Sprinkler Rough-in/Hydro8/5/20198/6/20198/6/2019PPART
DetailsTroy Cobbley
24 hour air test started on the dry system with 41psi on the guage.

Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
INSP-Sprinkler Rough-in7/11/20197/11/20197/11/2019PPASS
DetailsTroy Cobbley
Head added to the concealed area above fire place. Tenting passed. Piping for the west side tenant space can be covered. The center tenant space can not be covered until a tenting inspection has been completed.
INSP-Final7/11/20197/11/20197/11/2019PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian Inspection cancelled via mobile web on Thursday, July 11, 2019.
INSP-Sprinkler Rough-in6/25/20196/25/20196/25/2019PPART
DetailsJim Page
Tenting inspection for east side tenant space complete, all tenting in place for east side tenant at time of inspection, east side tenant space approved for cover.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in6/21/20196/24/20196/24/2019APASS
DetailsJim Page
Previously noted items have been corrected.

Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Bryan
INSP-Sprinkler Rough-in6/19/20196/20/20196/19/2019AFAIL
DetailsTroy Cobbley
EQ bracing on wet system main needs to be changed to what was approved. Dry system ok **MAS**
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in/Hydro6/19/20196/19/20196/19/2019PPASS
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Supply line flush5/17/20195/20/20195/20/2019APASS
DetailsTroy Cobbley
Underground supply line flush witnessed. Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in/Hydro4/11/20194/12/20194/12/2019APASS
DetailsTroy Cobbley
The underground hydro test was witnessed with no pressure loss.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in3/26/20193/27/20193/27/2019APASS
DetailsTroy Cobbley
Underground supply line cover passed.


Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
INSP-Sprinkler Rough-in3/26/20193/26/20193/26/2019PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
Staff review3/21/20193/21/20193/25/2019 PASS
DetailsMark Stumbaugh
Permit Ready to Issue  3/25/2019 DONE
Issue and Courier  3/25/2019 DONE
Issue and Courier  3/25/2019 DONE
didn't email Shelley because she emailed me that the customer was coming over to pick it up here-i did let hr know that there was a plan review fee since this is the 3rd resubmittal
Plan resubmittals received  3/21/2019 DONE
Resubmittals recieved 4 sets of the response letter & sheet FP3-took to MAS
Plan resubmittals received  3/7/2019 DONE
Resubmittals received 4 sets of drawings and 4 sets of calcs-took to MAS
Staff review3/1/20193/1/20193/5/2019 FAIL
DetailsMark Stumbaugh
See comments-3 hr plan review time
Plan resubmittals received  3/1/2019 DONE
resubmittals received-broke 1 permit into 3-resubmittals all the drawings for them-took to MAS
Miscellaneous action  3/1/2019 DONE
emailed Shelley Ste #'s and permits as well as the AF #er's
Staff review2/20/20192/20/20192/21/2019 FAIL
DetailsMark Stumbaugh
Review Time 1hr
Miscellaneous action  2/21/2019 DONE
emailed Shelley about the failed plan revied and the review time
Application received  2/20/2019  
Plan assigned to (Stumbaugh)2/20/2019    
DetailsMark Stumbaugh