INSP-Final | 6/20/2019 | 6/21/2019 | 6/21/2019 | A | DONE |
Troy Cobbley
|
|
|
life safety passed
Call prior to going Phone #: 2084077853 >> Inspection requested via mobile web by Laura Schulte
|
DOC - Permit Finaled | | | 6/21/2019 | | DONE |
|
|
|
Per Troy C, final inspection compelted and passed
|
INSP-Final | 6/12/2019 | 6/12/2019 | 6/12/2019 | P | FAIL |
Jim Page
|
|
|
Insulation is resting/covering numerous upright sprinkler heads in warehouse, insulation cannot be resting/covering sprinkler heads, insulation will need to be raised.
Call prior to going Phone #: 2089473955 >> Inspection requested via mobile web by David
|
Staff review | 3/27/2019 | 3/27/2019 | 3/27/2019 | | DONE |
Mark Scharfen
|
|
|
IFC Final Review 03.27.2019.pdf uploaded.
|
Permit Ready to Issue | | | 3/27/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 3/27/2019 | | DONE |
|
|
|
emailed Shelley permit was issued
|
Staff review | 3/13/2019 | 3/13/2019 | 3/26/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC 2nd review 03.26.2019.pdf uploaded.
|
Plan resubmittals received | | | 3/13/2019 | | DONE |
|
|
|
Resubmittals received through e plan-project info and plans and building fiure code review-assigned to Adele
|
Staff review | 4/3/2019 | 4/3/2019 | 3/5/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC Fire Review 03.05.2019.pdf uploaded and emailed to applicant.
|
Plan assigned to (Adele) | 2/26/2019 | | 3/5/2019 | | |
Mark Scharfen
|
|
|
|
Miscellaneous action | | | 2/26/2019 | | DONE |
|
|
|
emailed Shelley the NAF # and the app-took me longer than normal to put in because i was waiting for G.C. to reply to my emails
|
Application received | | | 2/26/2019 | | |
|
|
|
|