INSP-Final | 4/10/2019 | 4/11/2019 | 4/11/2019 | A | DONE |
Troy Cobbley
|
|
|
Life safety passed
Call prior to going Phone #: 2084738906 >> Inspection requested via mobile web by Gina or Naomi
|
DOC - Permit Finaled | | | 4/11/2019 | | DONE |
|
|
|
per troy c
|
INSP-Final | 4/5/2019 | 4/8/2019 | 4/8/2019 | A | FAIL |
Jim Page
|
|
|
Install code compliant door hardware on west exit doors, both doors have thumbturn deadboklts installed. Replace ceiling tile in storage room. Replace fire sprinkler head that has drywall texture/paint in "Powder room" restroom, fire sprinkler head must be replaced, not cleaned per NFPA 13. Remove 5113 address from north door, permit shows space as 5111 for address.
PLEASE CALL AHEAD OF TIME Phone #: 2084738906 >> Inspection requested via mobile web by Gina Clark
|
Staff review | 3/26/2019 | 3/26/2019 | 4/5/2019 | | DONE |
Mark Scharfen
|
|
|
|
Plan assigned to (Scharfen) | 3/26/2019 | | 4/5/2019 | | DONE |
Mark Scharfen
|
|
|
IFC Final Review 04.05.2019.pdf uploaded.
|
Permit Ready to Issue | | | 4/5/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 4/5/2019 | | DONE |
|
|
|
emailed Shelley that the permit is issued
|
Plan resubmittals received | | | 3/26/2019 | | DONE |
|
|
|
resubmittal received in e plan-assigned to MS
|
Staff review | 3/6/2019 | 3/6/2019 | 3/21/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC 1st review 03.21.2019.pdf uploaded and emailed to applicant.
|
Plan assigned to (Adele) | 3/6/2019 | | 3/21/2019 | | FAIL |
Mark Scharfen
|
|
|
|
Application received | | | 3/6/2019 | | |
|
|
|
|
Miscellaneous action | | | 3/6/2019 | | DONE |
|
|
|
emailed Shelley the NAF # and app
|